Chat with Sunniva on WhatsApp
Skip to Content

9.9 Compressor failures and their root causes

Key idea: Compressors rarely fail on their own; they are usually killed by something else in the system.

The compressor is the heart of the heat pump. When it fails, replacing it without finding the root cause often leads to a second failure within weeks. Always ask what made it fail.

Like a motorbike engine seized because the oil ran out, the engine is the victim, not the cause. The same is true for compressors.

Main failure types

Failure What happens Common root causes
Liquid floodback Liquid refrigerant enters the compressor and washes oil away Low superheat, overcharge, faulty expansion valve, low evaporator air or water flow
Liquid slugging A slug of liquid enters the compression chamber; mechanical damage Refrigerant migration during off cycle, no crankcase heater, poor piping
Overheating Motor and oil get too hot; oil breaks down Low charge, high superheat, high discharge pressure, high compression ratio
Oil loss Bearings run dry Oil trapped in system, long pipes without oil return, leaks, floodback
Electrical burnout Motor windings short to each other or to earth Voltage imbalance, single phasing, overheating, moisture and acid in system
Contamination Moisture, air or debris cause acid and wear Poor evacuation, open system left too long, no drier, brazing without nitrogen
How system faults kill compressors
How system faults kill compressors

Checks before condemning a compressor

Check How Typical result for healthy compressor
Winding resistance (single-phase: C-S, C-R, S-R; three-phase: between each pair) Multimeter, power isolated Three-phase windings equal within a few percent; single-phase S-R = C-S + C-R
Insulation resistance to earth Insulation tester at 500 V DC Above 1 MΩ minimum at 500 V DC (healthy compressors usually read well above 2 MΩ; follow the manufacturer's manual)
Running current Clamp meter on each phase Within nameplate RLA, balanced
Compression Pressure difference when running Normal discharge-suction difference for conditions
Oil condition Sample or acid test kit Clear, no burnt smell, acid test negative

After a burnout

  1. Recover refrigerant; do not vent.
  2. Test oil for acid.
  3. Replace compressor and filter-drier; fit a suction line filter-drier if acid is present.
  4. Pressure test with dry nitrogen; evacuate deeply (lesson 9.10).
  5. Weigh in correct charge.
  6. Check acid again after running; change drier again if needed.

Worked example — Voltage imbalance

Measured line voltages: 410 V, 400 V, 385 V.

Equation

Average = (410 + 400 + 385) ÷ 3 = 398.3 V Maximum deviation = 398.3 − 385 = 13.3 V Imbalance = 13.3 ÷ 398.3 × 100 = 3.3 %

Voltage imbalance above about 2 % is generally considered harmful to motors; the current imbalance it causes is several times larger. Get the supply checked before fitting a new compressor.

Remember

  • The compressor is usually the victim, not the culprit.
  • Floodback and overheating are the two biggest killers.
  • Check windings, insulation, current and oil before condemning.
  • After a burnout, clean the system or the new compressor will fail too.
Common mistake: Replacing a burnt compressor without changing the filter-drier and testing for acid.

Compressors rarely fail on their own; they are usually killed by something else in the system.

Rating
0 0

There are no comments for now.

to be the first to leave a comment.