Chat with Sunniva on WhatsApp
Skip to Content

9.1 Preventive maintenance schedule and service records

Key idea: A heat pump that is checked on a fixed schedule and logged every time rarely fails without warning.

Preventive maintenance (PM) means planned checks done before something breaks. Breakdown maintenance means repairing after a failure. PM costs less because small problems such as a dirty filter are fixed before they trip the compressor.

Think of a pressure cooker. You check the gasket and the whistle before cooking, not after the lid blows. A heat pump works the same way. Most failures start as a slow drift in a pressure, temperature or current.

A service record is the written history of a unit. Each visit you note readings, work done and parts changed. Over months the record shows trends, like a slowly rising discharge temperature, that a single visit cannot.

PM schedule

Frequency Who Check What "good" looks like
Daily Operator Unit running, no alarms on controller No active alarm; set point reached
Daily Operator Supply and return water temperature Difference (ΔT) typically 3–7 °C
Daily Operator Unusual noise, vibration, water drips None
Monthly Technician Clean Y-strainer on water inlet Mesh clear; pressure drop back to normal
Monthly Technician Clean air-coil fins (light wash) Fins clear of dust, leaves, lint
Monthly Technician Condensate drain and tray Free-flowing, no algae
Monthly Technician Water system pressure and air vents Pressure as commissioned; no trapped air
Quarterly Technician Suction and discharge pressures, superheat, subcooling Within commissioning values
Quarterly Technician Compressor and fan current on each phase Within nameplate; phases balanced within about 2–3 %
Quarterly Technician Tighten electrical terminals, inspect contactors No burnt marks, no pitting
Quarterly Technician Leak check on brazed joints and flare nuts No oil stains, detector silent
Quarterly Technician Water quality test (hardness, TDS, pH) Within limits of lesson 9.3
Yearly Technician Descale plate heat exchanger (more often in hard water) Approach temperature back to commissioning value
Yearly Technician Deep coil clean with coil cleaner Full air flow restored
Yearly Technician Insulation resistance test of compressor and fan motors Above 1 MΩ minimum at 500 V DC (healthy compressors usually read well above 2 MΩ; follow the manufacturer's manual)
Yearly Technician Calibrate or verify sensors and safety switches Readings match reference instrument; HP/LP switches trip at set point
Yearly Technician Expansion vessel pre-charge, safety valve, pump bearings Pre-charge as designed; valve not passing

What a service record must contain

Field Example
Date, site, unit serial 12-03-2026, Hotel, Pune, serial XXXX
Ambient and water temperatures Ambient 34 °C; water in 48 °C, out 54 °C
Suction and discharge pressure (R410A) 15.0 bar(g) / 35.0 bar(g)
Superheat and subcooling 6 K / 5 K
Compressor current (R/Y/B) 18.2 / 18.4 / 18.1 A
Alarms in log since last visit None
Work done, parts used Strainer cleaned; coil washed
Next action Descale PHE at next quarterly visit
The preventive maintenance cycle
The preventive maintenance cycle

Remember

  • PM is planned; breakdown repair is unplanned and costs more.
  • Record readings every visit so you can see trends.
  • Compare against commissioning values, not just "looks fine".
  • Hard water and dusty sites need shorter intervals.
Field tip: Photograph the controller's alarm log and the nameplate at every visit and attach them to the record.

A heat pump that is checked on a fixed schedule and logged every time rarely fails without warning.

Rating
0 0

There are no comments for now.

to be the first to leave a comment.