Chat with Sunniva on WhatsApp
Skip to Content

9.8 Low capacity and falling COP

Key idea: When capacity or COP falls, the cause is usually one of three: poor heat transfer, wrong charge, or a tired compressor.

Capacity is the heat output in kW. COP (coefficient of performance) is heat output divided by electrical input. A unit with COP 4 gives 4 kWh of heat for 1 kWh of electricity.

Falling COP often shows up first in the electricity bill, not as a fault code. The unit keeps running but heats slower and costs more. Like a fridge with a dirty back grill, it still cools but runs much longer.

Main causes

  • Dirty air coil or scaled PHE.
  • Low or high refrigerant charge.
  • Wrong water flow (too low or too high).
  • Expansion valve badly set or faulty.
  • Compressor wear: leaking valves or scroll tips cause low compression.
  • Reversing valve leaking hot gas internally into suction.
  • Wrong set point or poor controls (short cycling).
  • Unit running outside its design conditions (very cold or very hot water).
COP vs leaving water temperature, clean vs scaled
COP vs leaving water temperature, clean vs scaled

Symptom → cause → check → fix (capacity and COP)

Symptom Likely cause Check Fix
Slow heat-up, high discharge pressure, rising approach Scaled PHE Approach temperature Descale
Slow heat-up, low suction, high SH Low charge SH, SC, leak test Fix leak, recharge by weight
Low current, small pressure difference, normal charge Compressor wear / internal leak Compression ratio, current vs data Replace compressor (find root cause first)
Suction line warm in heating, both reversing valve outlets similar temperature Reversing valve leaking Temperatures at valve ports Replace reversing valve
Frequent start-stop Short cycling: small buffer, tight differential Controller log of starts per hour Adjust differential, add buffer volume
COP low only on very cold mornings Normal effect of low ambient Compare with manufacturer data Expected; check defrost and backup

Worked example — Measure field COP

A heat pump at a hostel in Bhopal. Water flow 2,000 LPH, in 45 °C, out 52 °C. Input power measured 4.2 kW.

Equation

ṁ = 2,000 ÷ 3,600 = 0.556 kg/s Q = 0.556 × 4.19 × (52 − 45) = 0.556 × 4.19 × 7 = 16.3 kW COP = 16.3 ÷ 4.2 = 3.9

If commissioning COP at the same conditions was 4.3, the drop is about 9 %. Daily cost impact for 10 hours at the example rate of ₹9/kWh: Input at COP 4.3 = 16.3 ÷ 4.3 = 3.79 kW; at COP 3.9 = 4.2 kW. Extra = 0.41 kW × 10 h × ₹9 = ₹37 per day, about ₹13,500 per year.

Remember

  • COP = heat out ÷ power in; measure both.
  • Compare at the same water and ambient conditions.
  • Small COP losses add up to large yearly costs.
  • Clean heat exchangers first; condemn the compressor last.
Common mistake: Measuring COP during a defrost cycle or right after start-up; wait for steady running.

When capacity or COP falls, the cause is usually one of three: poor heat transfer, wrong charge, or a tired compressor.

Rating
0 0

There are no comments for now.

to be the first to leave a comment.