How big a heat pump — and what puts the heat in?
Most sizing tools stop at the kilowatts. This one goes on to the part that decides whether the building is actually warm: the fan coils or radiant panels that move that heat into the room, and how much of their rated output survives on heat pump water rather than boiler water.
The space
How big it is, and how it is built.
Temperatures
The difference across the wall is what costs money.
How the heat gets in
Fan coils, or radiant panels with no fan.
The plant room
One machine or several, and whether you want a spare.
What you pay for energy
Change these to your own tariff.
Construction and comparison assumptions change only if you know why
Where the heat goes
Cost to run for one day
What it pays back, and what it stops
Want this sizing checked by an engineer?
Your name, phone and email go on the saved sheet and let our team confirm the load, the emitter selection and the pipe sizing against your actual building. All three are needed before the sheet can be sent or saved.
How this is worked out
- Heat loss = area × U-value × the inside-to-outside difference, summed over walls, glazing, roof and floor, plus 0.33 × air changes × volume × the same difference for the air. The ground floor is charged half the difference — the earth under a slab sits far nearer room temperature than the outside air does.
- Sizing is on the peak load, not on a run window. A hot water machine is sized on the day’s energy because storage rides the peak. A building loses heat at the design rate for as long as it is that cold, and no tank rides that out.
- Fan coils are forced convection: the fan sets the air-side heat transfer, so output is very nearly proportional to the water-to-room difference. That is why a fan coil copes with heat pump water while a radiator struggles. Sizing here is in tons of nominal cooling, because that is how fan coils are bought in India, with the heating output worked out from the coil’s sensible conductance.
- Radiant panels follow the EN 442 exponent of 1.3: natural convection and radiation both strengthen faster than the temperature difference itself, so output falls away sharply as the water cools. A panel rated at the standard 50 K difference gives well under half that on 50 °C heat pump water. This is the single commonest reason a heat pump installation fails to heat a building — panels sized off the catalogue figure.
- The water temperature is the design decision. Cooler water means a better COP and a cheaper bill, but bigger emitters. The slider makes that trade visible: move it and watch both the panel count and the running cost change.
- A buffer tank of 12 to 25 litres per kilowatt gives the defrost cycle somewhere to draw from and stops the compressor short-cycling against a small circuit.
- Machine selection interpolates each model’s own published capacity and COP to your design temperature. SE-AH is published down to 5 °C, SE-EVI down to −20 °C — which is why the recommendation moves to EVI as you drag the temperature down.
- U-values and emitter ratings are indicative, chosen for the construction type you picked. They are not Sunniva product data, and they are all sliders. Replace them with real figures before ordering; the saved sheet records exactly what was used.
- Payback is simple payback — the price you type in, divided by the annual saving. No finance, no maintenance, no discounting, and no price of ours is assumed or disclosed. Carbon is the displaced fuel’s emissions minus the electricity the heat pump draws, at the Indian grid average of 0.71 kg CO₂ per unit. Every factor is a slider, and the saved sheet records what was used.
- Indicative only. Room use, orientation, shading and occupancy all affect the real load — confirm with Sunniva Encon LLP before ordering.
Calculated for
What you entered
Result
Running cost & savings
How this was worked out
Talk to Sunniva
Contact
+91 93213 65103sales@sunnivaencon.com
www.sunnivaencon.com
Office
C‑443, Oshiwara Industrial Centre Premises CHS, New Link Road, Goregaon West, MumbaiHow big a heat pump — and what puts the heat in?
Most sizing tools stop at the kilowatts. This one goes on to the part that decides whether the building is actually warm: the fan coils or radiant panels that move that heat into the room, and how much of their rated output survives on heat pump water rather than boiler water.
The space
How big it is, and how it is built.
Temperatures
The difference across the wall is what costs money.
How the heat gets in
Fan coils, or radiant panels with no fan.
The plant room
One machine or several, and whether you want a spare.
What you pay for energy
Change these to your own tariff.
Construction and comparison assumptions change only if you know why
Where the heat goes
Cost to run for one day
What it pays back, and what it stops
Want this sizing checked by an engineer?
Your name, phone and email go on the saved sheet and let our team confirm the load, the emitter selection and the pipe sizing against your actual building. All three are needed before the sheet can be sent or saved.
How this is worked out
- Heat loss = area × U-value × the inside-to-outside difference, summed over walls, glazing, roof and floor, plus 0.33 × air changes × volume × the same difference for the air. The ground floor is charged half the difference — the earth under a slab sits far nearer room temperature than the outside air does.
- Sizing is on the peak load, not on a run window. A hot water machine is sized on the day’s energy because storage rides the peak. A building loses heat at the design rate for as long as it is that cold, and no tank rides that out.
- Fan coils are forced convection: the fan sets the air-side heat transfer, so output is very nearly proportional to the water-to-room difference. That is why a fan coil copes with heat pump water while a radiator struggles. Sizing here is in tons of nominal cooling, because that is how fan coils are bought in India, with the heating output worked out from the coil’s sensible conductance.
- Radiant panels follow the EN 442 exponent of 1.3: natural convection and radiation both strengthen faster than the temperature difference itself, so output falls away sharply as the water cools. A panel rated at the standard 50 K difference gives well under half that on 50 °C heat pump water. This is the single commonest reason a heat pump installation fails to heat a building — panels sized off the catalogue figure.
- The water temperature is the design decision. Cooler water means a better COP and a cheaper bill, but bigger emitters. The slider makes that trade visible: move it and watch both the panel count and the running cost change.
- A buffer tank of 12 to 25 litres per kilowatt gives the defrost cycle somewhere to draw from and stops the compressor short-cycling against a small circuit.
- Machine selection interpolates each model’s own published capacity and COP to your design temperature. SE-AH is published down to 5 °C, SE-EVI down to −20 °C — which is why the recommendation moves to EVI as you drag the temperature down.
- U-values and emitter ratings are indicative, chosen for the construction type you picked. They are not Sunniva product data, and they are all sliders. Replace them with real figures before ordering; the saved sheet records exactly what was used.
- Payback is simple payback — the price you type in, divided by the annual saving. No finance, no maintenance, no discounting, and no price of ours is assumed or disclosed. Carbon is the displaced fuel’s emissions minus the electricity the heat pump draws, at the Indian grid average of 0.71 kg CO₂ per unit. Every factor is a slider, and the saved sheet records what was used.
- Indicative only. Room use, orientation, shading and occupancy all affect the real load — confirm with Sunniva Encon LLP before ordering.
Calculated for
What you entered
Result
Running cost & savings
How this was worked out
Talk to Sunniva
Contact
+91 93213 65103sales@sunnivaencon.com
www.sunnivaencon.com