Key idea: A low-pressure trip means the evaporator is not getting enough heat or enough refrigerant.

The low-pressure (LP) switch sits on the suction line. It opens when suction pressure falls too low. This protects the compressor from running without enough refrigerant and the evaporator from freezing.

Imagine drinking through a straw from an almost empty glass. You suck harder and harder, but little comes. A starved evaporator is the same: the compressor pulls suction pressure down because too little vapour is coming in.

In heating mode the evaporator is the air coil. In cooling mode on a reversible unit, it is the water-side PHE.

Main causes

  • Low air flow over the air coil: dirt, ice, failed fan.
  • Heavy frosting without proper defrost.
  • Very low ambient temperature beyond the unit's operating range.
  • Low refrigerant charge (leak).
  • Blocked filter-drier or strainer in the liquid line.
  • Expansion valve stuck closed or faulty (or EEV driver fault).
  • In cooling: low chilled water flow, low set point, frozen PHE.
  • Faulty LP switch or sensor.
Low-pressure trip: decision tree
Low-pressure trip: decision tree

Symptom → cause → check → fix (low pressure)

Symptom Likely cause Check Fix
LP trip, high SH, low SC, oil stains Refrigerant leak Leak test (9.10) Repair leak, vacuum, weigh in charge
LP trip, high SH, normal SC, cold or frosty drier Blocked filter-drier Temperature drop across drier over about 2 K Replace drier
LP trip, high SH, normal SC, drier warm Expansion valve stuck closed Valve response, EEV coil and driver Replace valve or coil/driver
LP trip in heating, coil fully iced Defrost failure Defrost sensor, reversing valve, defrost logic Replace sensor or valve
LP trip, coil dirty, fan slow Low air flow Fan current, coil condition Clean coil, repair fan
LP trip in cooling, chilled water ΔT high Low water flow at evaporator Strainer, pump, valves Restore flow

Worked example — Check the drier

Liquid line temperature before the filter-drier: 38 °C. After it: 33 °C.

Equation

ΔT = 38 − 33 = 5 K. A healthy drier shows almost no drop (typically below about 1–2 K). A 5 K drop means it is blocked and the liquid is flashing. Replace the drier.

Remember

  • First ask: which coil is the evaporator right now?
  • High superheat plus low subcooling usually means low charge.
  • High superheat with normal subcooling points to a restriction.
  • Check air flow and ice before refrigerant.
Field tip: Feel along the liquid line; a sudden cold spot shows exactly where the restriction is.

A low-pressure trip means the evaporator is not getting enough heat or enough refrigerant.