Chat with Sunniva on WhatsApp
Skip to Content

5.2 Capacity vs ambient: derating

Key idea: As outdoor air gets colder, an air-source heat pump delivers less heat, so you size at the coldest design ambient.

An air-source heat pump picks up heat from the air. Colder air holds less heat for the evaporator to collect, and the compressor pumps less refrigerant mass because suction gas is less dense. Cold air simply has less heat to give, so the machine picks up less.

Derating means reducing the rated capacity to the real capacity at your design ambient. The design ambient is the low outdoor temperature you design for, for example the typical winter morning low at your site.

Typical Indian design ambients (illustrative, check local climate data):

City Typical winter design ambient Note
Chennai 18–20 °C Little derating
Mumbai 15–17 °C Little derating
Bengaluru 12–14 °C Mild
Delhi 4–6 °C Moderate, fog/frost mornings
Shimla −2 to 2 °C Strong derating, defrost
Leh −20 to −15 °C Needs cold-climate (EVI) unit
Capacity and COP vs ambient at 55 °C water
Capacity and COP vs ambient at 55 °C water

Worked example — derating for Delhi winter

A unit is rated 20 kW at 20 °C. Its table shows 82 % capacity at 5 °C with 55 °C water. Defrost loss is taken as 8 % (typical).

Equation

Qsite = 20 × 0.82 × (1 − 0.08) = 20 × 0.82 × 0.92 = 15.1 kW. The "20 kW" machine is a 15 kW machine on a Delhi January morning.

Remember

  • Size at design ambient, not at rating ambient.
  • Capacity and COP both fall with ambient.
  • Add defrost loss below about 7 °C in humid air.
  • In hot climates the unit has spare capacity in summer.
Field tip: Ask for the full capacity table, not the brochure single point.

As outdoor air gets colder, an air-source heat pump delivers less heat, so you size at the coldest design ambient.

Rating
0 0

There are no comments for now.

to be the first to leave a comment.