Chat with Sunniva on WhatsApp
Skip to Content

4.9 Cold climates and high altitude

Key idea: In cold air, an air-source heat pump loses capacity and COP and must defrost; at altitude, thinner air reduces airflow mass and boils water at lower temperatures.

As outdoor air gets colder, the evaporator has less heat to pick up. Capacity falls and COP falls. Below about 5 °C with humid air, ice forms on the coil. The unit must defrost, usually by briefly reversing the cycle.

Capacity and COP vs ambient at 45 °C outlet
Capacity and COP vs ambient at 45 °C outlet
Place (typical) Altitude Typical winter low Notes
Delhi ~220 m 3–7 °C Light frost risk, fog
Shimla ~2,200 m −2 to 2 °C Defrost frequent
Srinagar ~1,600 m −5 to −2 °C Glycol advisable
Leh ~3,500 m −15 to −25 °C Low-ambient design, glycol, back-up

Design rules for cold sites:

  • Size at the local design low, not at the rated 7 °C point.
  • Choose units built for low ambient (for example, vapour injection or CO₂ cycles).
  • Protect water circuits with glycol (antifreeze) or drain-down. About 30% ethylene glycol protects to roughly −15 °C; about 40% to roughly −24 °C (typical).
  • Glycol lowers heat transfer and raises pumping power; allow 5–10% derating (typical).
  • Keep snow and ice away from the coil and condensate drains.

At altitude the air is thinner. At about 3,500 m air density is roughly 70% of sea level. A fan moves the same volume but less mass, so coil capacity falls. Water boils at about 88–89 °C at that height, so keep vent and relief settings in mind.

Worked example — derating at Leh

A heat pump gives 20 kW at 7 °C ambient at sea level. At Leh, design ambient is −15 °C. Use capacity factor 0.62 (from the chart), altitude factor 0.90 and glycol factor 0.95 (typical assumptions; check maker data).

Equation

  • P = 20 × 0.62 × 0.90 × 0.95 = 10.6 kW
  • A 20 kW-rated unit gives only about 10.6 kW at Leh. Size accordingly.

Remember

  • Capacity and COP both fall as ambient falls.
  • Defrost cycles take a share of every cold hour.
  • Altitude reduces air mass flow and boiling point.
  • Always protect water circuits from freezing.
Field tip: Raise outdoor units at least 300–500 mm above expected snow level and keep the condensate drain heated.

In cold air, an air-source heat pump loses capacity and COP and must defrost; at altitude, thinner air reduces airflow mass and boils water at lower temperatures.

Rating
0 0

There are no comments for now.

to be the first to leave a comment.