Chat with Sunniva on WhatsApp
Skip to Content

7.4 Water piping layout and sizing

Key idea: The water side must carry the right flow at a sensible velocity, with every component in its correct place.

Flow rate is how much water passes per hour (m³/h or LPH, litres per hour). Velocity is how fast it moves in the pipe (m/s). Too fast is noisy and erodes fittings. Too slow lets air and dirt settle, and the pipe costs more than needed.

A typical heat pump circuit runs at a temperature difference (ΔT) of about 5 K between flow and return. The heat carried depends on flow and ΔT.

Typical installation P&ID: heat pump to storage tank
Typical installation P&ID: heat pump to storage tank

Flow direction: heat pump → flow pipe → tank coil / tank → return pipe → strainer → pump → non-return valve → heat pump.

Tag Item Purpose
HP-1 Heat pump Heat source
TK-1 Storage tank Stores hot water, buffers load
IV-1/2/3 Isolation valve (ball valve) Isolate unit or tank for service
FC-1/2 Flexible connector Stop vibration reaching pipes; allow small movement
YS-1 Y-strainer Catch dirt and scale before pump and heat exchanger
P-1 Circulation pump Moves water around the loop
NRV-1 Non-return valve Stops reverse flow when pump stops
EV-1 Expansion vessel Absorbs water expansion as it heats
SV-1 Safety (relief) valve Opens if pressure rises above set point
AV-1 Automatic air vent Releases trapped air at high point
DV-1/2 Drain valve Empty and flush the system
TT-1/2/3 Temperature transmitter / test point Read flow, return and tank temperatures
PT-1/2 Pressure transmitter / gauge point Read pressure; across strainer and unit shows blockage

Typical pipe sizing table

Water flow at typical velocities of 0.7–1.5 m/s, based on typical internal diameters of medium-grade steel pipe. Copper and PPR (polypropylene random copolymer) pipes have different internal diameters, so check the maker's chart. These are typical guides, not design values.

Nominal size Typical ID (mm) Flow at 0.7 m/s (m³/h) Flow at 1.5 m/s (m³/h) Approx. heat at ΔT 5 K, upper flow (kW)
DN15 (½") 16 0.5 1.1 6
DN20 (¾") 22 0.9 2.0 11
DN25 (1") 27 1.5 3.2 18
DN32 (1¼") 36 2.6 5.5 32
DN40 (1½") 42 3.5 7.5 43
DN50 (2") 53 5.6 12.0 70
DN65 (2½") 69 9.4 20.1 117
DN80 (3") 81 13.0 27.8 160
DN100 (4") 105 21.9 47.0 270

Small pipes near homes are best kept at the lower end of velocity for quiet running.

Worked example — size the pipe for a 30 kW heat pump at a Bengaluru hotel

The unit heats at 30 kW with ΔT = 5 K.

Equation

  1. Flow: 30 ÷ (1.163 × 5) = 30 ÷ 5.815 = 5.16 m³/h (5,160 LPH).
  2. Try DN32 (ID 0.036 m): area = 0.7854 × 0.036² = 0.00102 m². Velocity = 5.16 ÷ (3,600 × 0.00102) = 1.41 m/s. Upper end, possible but noisier.
  3. Try DN40 (ID 0.042 m): area = 0.7854 × 0.042² = 0.00139 m². Velocity = 5.16 ÷ (3,600 × 0.00139) = 1.03 m/s. Comfortable.
  4. Choose DN40 for the main run. The unit's own connection may be smaller; reduce only at the unit.

(1.163 is the heat in Wh needed to warm 1 litre of water by 1 K.)

Remember

  • Flow = kW ÷ (1.163 × ΔT); then pick a pipe for about 0.7–1.5 m/s.
  • Strainer and pump on the return, before the heat pump.
  • Air vents at high points, drains at low points.
  • Fit TT and PT points on flow and return for commissioning.
Common mistake: Matching the main pipe to the unit's small connection size. Over a long run that starves the unit of flow and trips it on high pressure.

The water side must carry the right flow at a sensible velocity, with every component in its correct place.

Rating
0 0

There are no comments for now.

to be the first to leave a comment.