Chat with Sunniva on WhatsApp
Skip to Content

8.5 Calculating actual capacity and COP on site

Key idea: Capacity is water flow × specific heat × temperature rise; COP is that capacity divided by electrical input.

Heating capacity is the heat the unit puts into the water, in kW. Specific heat (cp) is the energy needed to warm 1 kg of a substance by 1 K. For water it is about 4.18 kJ/kg·K.

COP (coefficient of performance) is heat out divided by electricity in. A COP of 3.5 means 3.5 kW of heat for every 1 kW of electricity. The extra heat comes free from the outdoor air.

An electric geyser has a COP of about 1. That is why a heat pump can cut water heating electricity by two-thirds or more.

Energy balance from site readings
Energy balance from site readings

Equation

Equation

Shortcut for water (flow in LPH):

Equation

Worked example 1 — Circulating heat pump at a hotel in Pune

Site readings after 30 minutes of steady running. Ambient (TT-03) 28 °C. Inlet water (TT-01) 50.0 °C. Outlet water (TT-02) 55.0 °C. Flow (FT-01) 1.8 m³/h. Power meter (JQ-01) 3.10 kW.

Step 1 — mass flow. 1.8 m³/h = 1800 L/h. Water at this temperature is close to 1 kg/L.

Equation

Step 2 — temperature rise.

Equation

Step 3 — capacity.

Equation

Check with the shortcut: 1800 × 5 / 860 = 10.47 kW. Same answer.

Step 4 — COP.

Equation

Step 5 — compare. Look up the manufacturer's data at 28 °C ambient and 55 °C outlet, not the headline rating. If the data shows about 10.5 kW and COP 3.4 at these conditions, the unit is performing as expected.

Step 6 — what it saves (example rate ₹9/kWh). Over 8 running hours the unit delivers 10.45 × 8 = 83.6 kWh of heat for 3.10 × 8 = 24.8 kWh of electricity. That costs 24.8 × 9 = ₹223. An electric geyser would use about 83.6 kWh, costing about ₹752.

Worked example 2 — Tank heat-up method at a home in Bengaluru

When no flow meter is available, time a tank heat-up. A 500 L tank is heated from 25 °C to 55 °C in 1.5 hours. The energy meter shows 4.2 kWh used.

Equation

Equation

Equation

Equation

This method ignores tank heat loss and assumes the tank is well mixed. It gives a fair average, not an exact figure. Make sure no water is drawn off during the test.

Error source Effect on result How to avoid
Probes not matched ΔT wrong, capacity off by 5–10% Bucket test, note offset
Reading during defrost or start-up Capacity too low Wait for steady state
Flow meter in turbulent spot Flow wrong Use straight pipe run
Measuring amps, not kW Power wrong (power factor ignored) Use a true-RMS power meter
Comparing to rating at different conditions False "underperforming" claim Compare at the same ambient and water temperature

Remember

  • Q = ṁ · cp · ΔT; for water, kW = LPH × ΔT / 860.
  • Always compare site results with data at the same ambient and water temperatures.
  • Take readings only in steady state, never during defrost.
  • Small ΔT errors make big capacity errors; calibrate probes.
Common mistake: Using the nameplate input power instead of the measured power. Nameplate values are at rating conditions, not today's site conditions.

Capacity is water flow × specific heat × temperature rise; COP is that capacity divided by electrical input.

Rating
0 0

There are no comments for now.

to be the first to leave a comment.