10.5 CO₂ (R744) systems

Key idea: CO₂ is non-flammable and has GWP 1, but it runs at very high pressure and often above its critical point.

CO₂'s critical point is about 31 °C and 73.8 bar. Above this point there is no separate liquid and vapour. Heat is rejected in a "gas cooler" instead of a condenser.

This is called a transcritical cycle. Because the hot gas cools over a wide temperature glide, CO₂ heats water very well from a cold inlet to 65–90 °C. That suits sanitary hot water.

Typical pressures (approximate): gas cooler side 80–130 bar, evaporator side 25–45 bar. Standstill pressure on a warm Indian day can exceed 60 bar.

CO₂ transcritical cycle
CO₂ transcritical cycle
Property R744 (CO₂) R410A (for comparison, typical)
Safety class A1 A1
GWP 1 ~2000
High-side pressure 80–130 bar 25–35 bar
Critical temperature ~31 °C ~71 °C
Best use Hot water, large water temperature lift Space heating and cooling

Safety: high pressure needs rated pipes, fittings and gauges. CO₂ is heavier than air and displaces oxygen in pits and plant rooms. Dry ice can form when liquid CO₂ is vented quickly, blocking lines.

Remember

  • Use gauges and hoses rated for CO₂ pressures.
  • Vent CO₂ slowly to avoid dry ice formation.
  • Fit a CO₂ detector in enclosed plant rooms.
  • Efficiency depends strongly on cold water inlet temperature.
Common mistake: Using a standard HFC manifold on a CO₂ system — it is not rated for the pressure.