Sunniva Encon LLP · Application NoteAN-091 · Rev 0 · 23 Oct 2026
Evaporation and separation

CO₂ capture solvent regenerated with heat-pump steam

How a plant capturing 3 tonnes of CO₂ a day from boiler flue gas can supply its stripper reboiler with low-pressure steam from a heat pump running on stripper cooling water, and what it saves against a furnace-oil fired steam boiler.

Application#91 Regenerating solvent in CO₂ capture
Temperature band100–120 °C
Sunniva selection5 × SE-WWUHT-27
Replacesfurnace-oil fired steam boiler

▶Video: Low-pressure steam from waste heat

V07 · 2–2.5 min
Low-pressure steam from waste heat

Water-source R245fa heat pumps making 2 bar steam up to 120 °C

Video coming soon

01Problem statement

  • Regeneration is the main energy cost. Stripping CO₂ from the solvent takes most of the energy in capture, usually supplied as steam from a fired boiler.
  • Heat leaves through the coolers. The stripper overhead condenser and lean-amine cooler reject heat at 55–70 °C to the cooling tower.
  • Burning fuel to capture CO₂. A fuel-fired boiler for the reboiler adds CO₂ of its own, which cuts the net capture.
  • Losses between fuel and process. Burning furnace oil in a boiler or heater and distributing the heat loses a quarter or more of the fuel's energy before it reaches the process.
  • Compliance, safety and handling. Fired equipment brings boiler inspections, fuel storage and unloading, flue emissions and an attendant on every shift.

02Use case

The reference plant captures about 3 tonnes a day of CO₂ from its boiler flue gas for food-grade and industrial CO₂ sales. It uses an advanced amine solvent that regenerates at 105–110 °C and runs round the clock.

Heat userProcess temp.BasisHeat, kWh/day
Stripper reboiler duty105–110 °C3 t CO₂/day × 2.8 GJ/t2,333
CO₂ dryer regeneration gas heatingGas 30 → 110 °C150 m³/h × 1.9 kg/m³ × 0.85 kJ/kg·K × 80 K × 8 h43
Storage and pipework standing losses–about 5%119
Total useful heat2,495

Averaged over 20 running hours, the heat pumps need about 125 kW.

03P&ID

L-101 · Hot primary · 120 °CTT103L-102 · Return · ~90 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101…105SE-WWUHT-27 · 27 kWP-100SRC-100stripper overheadcondenser andlean-amine coolerwaterheat source ~58 °CWater-sourceSG-101flash steamgenerator2 bar gsafety valvePT101TT102LT101softenerfeedwater make-upL-201 · Steam header · 2 bar gTCV-201TIC201RB-201Stripper reboiler110 °Clean amine 105 °Cto stripper 110 °CTCV-202TIC202DR-202CO₂ dryer regen heater110 °CP-201 condensateL-202 · Condensate returnNCB-001 existing FO boilerstandby / top-up onlysteam / hot supplyreturnsignalsource waterpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-091 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • 5 × SE-WWUHT-27 (135 kW total) (SE-WWUHT water-source, R245fa) delivering 120 °C, covering the day's 2,495 kWh in about 18.5 running hours.
  • Heat source: stripper overhead condenser and lean-amine cooler water at about 58 °C. Cooling the stripper overhead and lean amine is a by-product, which cuts cooling-tower load and solvent losses.
  • The furnace-oil fired steam boiler stays connected behind a normally closed valve as standby.
  • Cooling water from the stripper overhead condenser and lean-amine cooler, at about 58 °C, feeds the steam-generating heat pump evaporator.
  • The heat pump makes 2 bar steam at about 120 °C for the stripper reboiler and the CO₂ dryer regeneration heater.
  • The existing boiler steam header stays connected through a pressure-reducing station as standby.

Selected equipment

ModelSE-WWUHT-27 × 5
Heating capacity27 kW each, 135 kW total
COP2.93 at the data sheet's rated condition (60/55 °C source water)
Power inputabout 46.0 kW total at rated conditions
Ratingwater or steam to 120 °C, R245fa
Supply temperature120 °C
Steam40 kg/h at 2 bar per SE-WWUHT-27 module

Ratings from the Sunniva TDS 2026 data sheets.

Control philosophy

The heat pump holds steam header pressure at 2 bar, and the boiler PRV is set slightly lower so it opens only if the heat pump cannot keep up. The reboiler controller sets steam flow to hold stripper bottom temperature. The cooling tower stays on the overhead condenser to take any heat the heat pump does not use.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per tonne of CO₂––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

Higher net capture

Less fuel burnt for regeneration means less new CO₂ to capture.

Heat recycled in the loop

Heat from the overhead condenser and lean-amine cooler is returned to the reboiler.

Smaller cooling tower load

The overhead and lean-amine coolers send less heat to the tower.

Lower energy cost

Each kWh of electricity delivers about 2.9 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

No flame on site

No burner, flue or fuel tank for this duty, and no fuel deliveries to schedule.

Built-in redundancy

Several machines share the load. If one is serviced, the others and the storage carry most of the day, with the existing heater in reserve.

07Engineering pointers

Site data to collect

  • CO₂ capture rate and solvent type
  • Reboiler temperature and steam use
  • Overhead condenser and lean-amine cooler duties and temperatures
  • Boiler fuel use for the capture plant
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access

Design notes

  • Solvent choice sets the limit. Heat-pump steam at about 120 °C suits solvents that regenerate at 105–110 °C. Confirm reboiler temperature with the solvent supplier.
  • Amine on the source side. Keep an isolating exchanger between amine coolers and the heat pump so no amine reaches the heat pump.
  • Electrical. About 46 kW of heat pump input at rated conditions, plus pumps and fans. Check spare sanctioned load before ordering.
  • Source stream. The source must give up roughly two-thirds of the heat delivered. Confirm its flow and temperature over a full production day, and filter it before the evaporator.
  • Water quality. Scale forms quickly above 60 °C. Use softened make-up and keep the heat pump loop closed, with process fluids on the far side of an exchanger or coil.

Service and warranty

Sunniva has supplied 5,000+ heat pumps since 2012, with nine service technicians across India, including remote sites such as Leh. All components carry a one-year warranty.