Sunniva Encon LLP · Application NoteAN-092 · Rev 0 · 23 Oct 2026
Energy, utilities and waste heat

Boiler make-up water preheated by heat pumps

How a plant with a 5 tonne-per-hour steam boiler and poor condensate return can preheat make-up water to 85 °C with heat pumps, and what it saves against firing the furnace-oil boiler for that heat.

Application#92 Preheating boiler feedwater and make-up water
Temperature band80–90 °C
Sunniva selection3 × SE-SHT-50C
Replacesfurnace-oil fired steam boiler

▶Video: Process heat for engineering and utilities

V06 · 2–2.5 min
Process heat for engineering and utilities

Plating, phosphating, washers, curing and boiler feedwater

Video coming soon

01Problem statement

  • Cold make-up costs fuel. Every litre of make-up water heated from 30 °C inside the boiler uses expensive furnace oil.
  • Cold feed tank holds oxygen. A feed tank below 80 °C holds more dissolved oxygen, which causes pitting in the boiler and feed lines.
  • Live steam heating wastes steam. Plants often heat the feed tank with live steam, which uses boiler output that could go to process.
  • Losses between fuel and process. Burning furnace oil in a boiler or heater and distributing the heat loses a quarter or more of the fuel's energy before it reaches the process.
  • Compliance, safety and handling. Fired equipment brings boiler inspections, fuel storage and unloading, flue emissions and an attendant on every shift.

02Use case

The reference plant runs a 5 tonne-per-hour furnace-oil steam boiler for about 20 hours a day. Only 60% of condensate returns, so about 2 m³ of cold make-up water enters the feed tank every hour.

Heat userProcess temp.BasisHeat, kWh/day
Make-up water preheat30 → 85 °C2 m³/h × 20 h = 40,000 L/day, 30 → 85 °C2,554
Feed tank top-up heating60 → 85 °C10,000 L/day returned condensate and mixed feed, 60 → 85 °C290
Storage and pipework standing losses–about 5%142
Total useful heat2,987

Averaged over 20 running hours, the heat pumps need about 149 kW.

03P&ID

L-101 · Hot primary · 95 °CTT103L-102 · Return · ~71 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101SE-SHT-50C · 50 kWHP-102…103SE-SHT-50C · 50 kWAir-source, outdoorTK-1014,500 L95 °CinsulatedventTT101TT102LT101softenermake-up waterVFDP-102A/BL-201 · Supply header · 93 °CTCV-201TIC201PHE-201Make-up preheater85 °Csoft water 30 °Cto feed tank 85 °CTCV-202TIC202TK-202Boiler feed tank85 °CL-202 · Return header · ~71 °CNCB-001 existing FO boilerstandby / top-up onlyhot supplyreturnsignalpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-092 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • 3 × SE-SHT-50C (150 kW total) (SE-SHT cascade heat pump) delivering 95 °C, covering the day's 2,987 kWh in about 19.9 running hours.
  • A 4,500 L insulated storage tank decouples the heat pumps from the process peaks.
  • The furnace-oil fired steam boiler stays connected behind a normally closed valve as standby.
  • Softened make-up water passes through a plate exchanger heated with 95 °C water before entering the feed tank.
  • A coil in the feed tank holds it at 85 °C, replacing live steam sparging.
  • The boiler's own steam sparge stays in place as standby.

Selected equipment

ModelSE-SHT-50C × 3
Heating capacity50 kW each, 150 kW total
COP2.6 at A20 °C / W90 °C (data sheet T1)
Power inputabout 55.8 kW total at rated conditions
Ratingcascade R410A + R515B, rated 90 °C, 95 °C maximum
Supply temperature95 °C
Storage4,500 L insulated tank

Ratings from the Sunniva TDS 2026 data sheets.

Control philosophy

TT-101 at the tank top starts the heat pumps below 90 °C and stops them at 95 °C. TIC-201 holds make-up water leaving PHE-201 at 85 °C. TIC-202 holds the feed tank at 85 °C and opens the steam sparge valve only if the tank falls below 80 °C.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per tonne of steam––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

Direct fuel saving

Each degree of feed temperature the heat pump supplies is heat the boiler no longer burns oil for.

Less dissolved oxygen

A hot feed tank holds less oxygen, which reduces corrosion and oxygen scavenger dosing.

More steam for process

Steam once used to heat the feed tank goes to production instead.

Lower energy cost

Each kWh of electricity delivers about 2.6 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

No flame on site

No burner, flue or fuel tank for this duty, and no fuel deliveries to schedule.

Built-in redundancy

Several machines share the load. If one is serviced, the others and the storage carry most of the day, with the existing heater in reserve.

07Engineering pointers

Site data to collect

  • Boiler capacity, pressure and running hours
  • Condensate return percentage and temperature
  • Make-up water flow and feed tank temperature
  • Monthly furnace oil consumption
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access
  • Winter minimum ambient at site

Design notes

  • Feed pump NPSH. Hotter feedwater reduces NPSH available. Check the feed pump suction head and tank elevation before raising feed temperature.
  • Economiser. If the boiler has an economiser, hotter feedwater raises stack temperature. Check acid dew point and the overall saving.
  • Use softened water. Preheat after the softener only, so the exchanger does not scale.
  • Electrical. About 56 kW of heat pump input at rated conditions, plus pumps and fans. Check spare sanctioned load before ordering.
  • Winter output. The SE-SHT cascade gives about 80% of rated output at 7 °C ambient and still runs at −20 °C. Size on the coldest design day for northern sites.
  • Water quality. Scale forms quickly above 60 °C. Use softened make-up and keep the heat pump loop closed, with process fluids on the far side of an exchanger or coil.