Sunniva Encon LLP · Application NoteAN-090 · Rev 0 · 23 Oct 2026
Evaporation and separation

Low-temperature MED desalination driven by a heat pump

How a coastal plant making 20 m³ of distilled water a day in a low-temperature MED unit can drive it with a water-source heat pump on the final condenser water, and what it saves against a diesel-fired hot-water generator.

Application#90 Thermal desalination (MVC / MED)
Temperature band60–70 °C
Sunniva selection5 × SE-WWUHT-27
Replacesdiesel-fired hot-water generator

▶Video: Waste-heat recovery heat pumps

V10 · 2–2.5 min
Waste-heat recovery heat pumps

Lifting warm water from condensers, effluent and process cooling to useful heat

Video coming soon

01Problem statement

  • MED needs a heat source. Low-temperature MED needs hot water at 70–75 °C, and without plant waste heat this comes from a fuel-fired heater.
  • Condenser heat is rejected to sea. The final condenser rejects heat at 35–45 °C, close to the amount the first effect takes in.
  • Fuel per cubic metre. Fuel makes up most of the running cost of each cubic metre of distillate.
  • Losses between fuel and process. Burning diesel in a boiler or heater and distributing the heat loses a quarter or more of the fuel's energy before it reaches the process.
  • Compliance, safety and handling. Fired equipment brings boiler inspections, fuel storage and unloading, flue emissions and an attendant on every shift.

02Use case

The reference plant is a coastal process plant that needs about 20 m³ a day of high-purity distillate for boiler feed and process use. It runs an 8-effect low-temperature MED unit with a top brine temperature of about 65 °C.

Heat userProcess temp.BasisHeat, kWh/day
MED first-effect heat inputHot water 72 → 67 °C20 m³/day distillate × 2,330 kJ/kg ÷ GOR 71,849
Feed seawater final heating to top brine temperature58 → 65 °C50,000 L/day feed, ρ 1.025, cp 3.95, 58 → 65 °C394
Storage and pipework standing losses–about 5%112
Total useful heat2,355

Averaged over 20 running hours, the heat pumps need about 118 kW.

03P&ID

L-101 · Hot primary · 75 °CTT103L-102 · Return · ~56 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101…105SE-WWUHT-27 · 27 kWP-100SRC-100MED final-condensercooling waterheat source ~40 °CWater-sourceTK-1014,500 L75 °CinsulatedventTT101TT102LT101softenermake-up waterVFDP-102A/BL-201 · Supply header · 73 °CTCV-201TIC201PHE-201MED 1st-effect heater65 °C brineHW in 75 °CHW out 68 °CTCV-202TIC202PHE-202Feed seawater heater65 °CL-202 · Return header · ~56 °CNCB-001 existing diesel boilerstandby / top-up onlyhot supplyreturnsignalsource waterpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-090 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • 5 × SE-WWUHT-27 (135 kW total) (SE-WWUHT water-source, R245fa) delivering 75 °C, covering the day's 2,355 kWh in about 17.4 running hours.
  • A 4,500 L insulated storage tank decouples the heat pumps from the process peaks.
  • Heat source: MED final-condenser cooling water at about 40 °C. The heat pump takes over part of the final condenser duty, so less seawater has to be pumped for cooling.
  • The diesel-fired hot-water generator stays connected behind a normally closed valve as standby.
  • Part of the final-condenser cooling water, at about 40 °C, is routed through the heat pump evaporator.
  • The heat pump returns that heat at 75 °C to the first-effect heater and the final feed heater.
  • MVC units already use their own mechanical compression. This note covers MED plants driven by hot water.

Selected equipment

ModelSE-WWUHT-27 × 5
Heating capacity27 kW each, 135 kW total
COP2.93 estimated for a 40 °C source (the data sheet is rated on a 60/55 °C source)
Ratingwater or steam to 120 °C, R245fa
Supply temperature75 °C
Storage4,500 L insulated tank

Capacity is sized from the heat demand above. COP is an estimate until Sunniva engineering confirms the design.

Control philosophy

TT-101 at the tank top starts the heat pump below 70 °C and stops it at 75 °C. TIC-201 holds top brine temperature at 65 °C by modulating hot water to the first effect. TIC-202 holds feed seawater temperature. The diesel heater stays connected as standby.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per m³ of distilled water––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

Heat recycled within the plant

Heat the condenser would reject is lifted and used again in the first effect.

Low scaling regime

Running the first effect at 65 °C keeps the MED in a low-scaling temperature range.

Less cooling seawater

With the heat pump taking part of the condenser duty, less seawater needs pumping for cooling.

Lower energy cost

Each kWh of electricity delivers about 2.9 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

No flame on site

No burner, flue or fuel tank for this duty, and no fuel deliveries to schedule.

Built-in redundancy

Several machines share the load. If one is serviced, the others and the storage carry most of the day, with the existing heater in reserve.

07Engineering pointers

Site data to collect

  • Distillate demand and quality
  • MED effects, GOR and top brine temperature
  • Condenser cooling water flow and temperatures
  • Current heat source and fuel use
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access

Design notes

  • Seawater materials. Use titanium on all seawater and brine-side exchangers and an isolating loop between the condenser water and the heat pump.
  • Antiscalant and venting. Keep antiscalant dosing and non-condensable venting unchanged. They matter more than the heat source for MED reliability.
  • Source stream. The source must give up roughly two-thirds of the heat delivered. Confirm its flow and temperature over a full production day, and filter it before the evaporator.
  • Water quality. Scale forms quickly above 60 °C. Use softened make-up and keep the heat pump loop closed, with process fluids on the far side of an exchanger or coil.
  • Performance figure. The COP on this page is an engineering estimate, not a data sheet value. Sunniva engineering will confirm it for the actual source and supply temperatures.