Technical Data Sheet · Ultra High Temperature Heat Pump
SE-WWUHT Series

SE-WWUHT-50

Water-to-water single-cycle heat pump delivering pressurised hot water to 125 °C. R245fa, three-phase. Both sides are water — there is no air coil and no fan.

Sunniva SE-WWUHT-50 heat pump unit
Heating capacity
49.7kW
At T1 · Rated duty
Peak COP
2.99
At T1 · Rated duty
Max water temp
125°C
Rated outlet
Cooling capacity
32.9kW
Simultaneous, at the rated duty

Performance

Rated output at each published test condition
T1 Rated duty
Heating capacity
49.7kW
Power input
16.6kW
COP
2.99
Water flow
8.6m³/hr

Technical specifications

SE-WWUHT-50
Technical specifications for SE-WWUHT-50
ParameterUnitSpecification
Electrical supply
Power supply—380~415 V / 50 Hz / 3 Ph
Rated input powerkW16.6
Rated currentA34.27
Refrigeration circuit
Compressor—Scroll (Xecom)
Number of compressorsNos1
Refrigerant—R245fa
Heat exchanger (condenser)—Brazed plate heat exchanger
Throttling device—Electronic expansion valve
Water circuit
Maximum water temperature°C125
Water flowm³/hr8.6
Water pipe sizeinchR1-1/2
Rated pressurebar2
Unit & acoustics
Dimensions (L × W × H)mm1550 × 780 × 850
Net weightkg400
Noise at 1 metredB(A)≤ 62

Test conditions

  • Rated duty — evaporator side in / out 60 / 55 °C, condenser side in / out 115 / 120 °C

Installation requirement

  • Protection device and cable size are not published for this model. Confirm both with Sunniva before wiring — the rated current above is not sufficient to size them.
  • Maintain water flow of 8.6 m³/hr through the unit.

Built to order

Options available on this model

Options

  • Water connection — Coupling type to suit the site — threaded, flanged or grooved.
  • Casing — Stainless steel or powder-coated finish.
  • Circulation pump — Can be built into the unit instead of being fitted in the plant room.
  • Condenser — Stainless steel or copper, in place of the standard build.

How to order them

  • None of the above is the standard build, and none of it is included in the specification table on this page.
  • Ask for it at enquiry and have it confirmed in writing on the order acknowledgement. Price, lead time and weight can all change with it.

The table above describes the standard machine. Options are quoted per order and are available across the range except on the All-in-One and Split units.

Site installation schematic

How the source loop and the delivery loop connect on site
SE-WWUHTSE-WWUHT-50No fan · no air clearanceHEAT SOURCEProcess return, condenserwater, or another heatpump’s reject sideIVYP1PIIV60 °C in55 °C back to sourcePROCESS LOAD120 °C pressurisedhot water at 2 bar— not steamIVPIPRVP2Y120 °C out115 °C returnExpansion vesselExpansion vesselWarm source flowCooled source returnHot water to processIV isolation valve · Y strainer · P circulating pump · PI pressure indicator · PRV pressure relief valveThere is no storage tank, no cold water feed and no potable draw-off on this machine.Both circuits are closed and both must be running before the compressor will start.

Indicative hookup only. Static head, draw pattern and local code may call for additional components — confirm the final scheme with Sunniva before ordering.

Selection & site preparation

Recommended sizing derived from this model’s rated data
System sizing
Source loop flow8.6 m³/hr through the evaporator
Heat the source must give up32.9 kW at the rated duty. This is not optional — if the source cannot release it, the machine makes less heat than the nameplate.
Minimum source temperatureConfirm with Sunniva. The R245fa compressor window starts at 22 °C evaporating; too cold a source puts the machine outside its permitted envelope, not merely off its rating.
Delivery loop flow8.6 m³/hr through the condenser
Pipe size, both loopsR1-1/2
Line insulationBoth loops, rated for 125 °C on the delivery side
Civil & electrical
Unit footprint & dry weight1550 × 780 mm  ·  400 kg
Plinth1700 × 930 × 150 mm RCC, M20
Plinth level100 mm above finished floor, ± 3 mm/m
Clearances600 mm all round for service access. No air clearance is required — there is no fan.
ElectricalNot published for this model — confirm with Sunniva

Installation steps

Follow in order — a commissioning engineer should sign off before start-up
  1. Cast the plinth 1700 × 930 × 150 mm in M20 concrete, 100 mm above finished floor. Indoor or under cover; this machine does not need to see outdoor air.
  2. Set the unit on anti-vibration pads and level it to ± 3 mm/m.
  3. Pipe the source loop from the process return through an isolation valve, a Y-strainer and the circulating pump into the evaporator, and return it to the source. Size for 8.6 m³/hr.
  4. Pipe the delivery loop from the condenser to the process load and back, with an isolation valve, pressure indicator and a pressure relief valve on the flow. The circuit is pressurised — treat it as a hot water system, not a steam one.
  5. Fit an expansion vessel on each loop, sized to the loop volume and its working temperature. The delivery side runs at up to 125 °C.
  6. Fit a flow switch in each loop and interlock both to the compressor. Neither loop may be dry when the machine starts.
  7. Insulate both loops. The delivery side is a burn risk at 120 °C.
  8. Confirm the protection device and cable with Sunniva before wiring — they are not published for this model.
  9. On commissioning, prove the source can hold its temperature at full duty before signing off the heating output.

Process & instrumentation diagram

Refrigeration circuit, instrumentation and water connections
EVAPORATORBrazed plateCONDENSERBrazed plateCOMPRESSORScroll · R245faELECTRONIC EXPANSION VALVELiquid lineSuction vapourDischarge · hot gasLiquid lineWARM SOURCE IN · 60 °CCOOLED WATER OUT · 55 °CProcess return, condenser water,or the reject side of another heat pumpHOT WATER OUT · 120 °CRETURN · 115 °CPressurised to 2 bar — not steamP1P2No air-side coil and no fan. Both sides of this machineare water, and the source circuit is not optional.

Instrument schedule

Tags as marked on the diagram above
TagDeviceFunction
TT 01Compressor discharge temperatureDischarge superheat & high-temperature cut-out
TT 02Compressor suction temperatureSuction superheat monitoring
TT 03Water outlet temperatureSet-point control
TT 04Water inlet temperatureReturn water sensing, ΔT calculation
PS HIGHHigh-pressure switchDischarge over-pressure cut-out
TagDeviceFunction
PS LOWLow-pressure switchLoss-of-charge / low-suction cut-out
PI HPHigh-side pressure gaugeDischarge pressure indication
PI LPLow-side pressure gaugeSuction pressure indication
FS 01Water flow switchInterlock — no-flow lockout

Cabinet reference drawing

Typical general arrangement — this model’s own dimensions alongside
Reference general-arrangement drawing, Twin-compressor cabinet, vertical discharge
Dimensions (L × W × H)1550 × 780 × 850 mm
Net weight400 kg
Reference arrangement only — Twin-compressor cabinet, vertical discharge. Dimensions printed on the drawing are indicative; the figures above and in the specification table are the ones that apply to this model.

Operating envelope

The compressor’s permitted window, in refrigeration terms
Operating envelope · R245fa circuit Condensing against evaporating temperature — the compressor’s permitted operating window
135 °C max condensing 708090100110120130140 20304050607080 Tc °C CONDENSING Te °C EVAPORATING Normal operation
Envelope limits
Evaporating temperature Te22 °C to 75 °C
Condensing temperature Tc75 °C to 135 °C
Peak condensing135 °C highest hot-water temperature the circuit can reach
Transient operationNot applicable the envelope above is the continuous operating window

Reading the envelope

  • Te (evaporating) follows the source the unit draws heat from — the colder the air or source water, the lower Te sits.
  • Tc (condensing) follows the water leaving the unit — asking for 80 °C hot water puts Tc near the top of the envelope.
  • A duty is valid only inside the shaded area. A cold source combined with very hot water pushes the point towards the top-left, which is exactly where the envelope closes in — that corner is the real limit on winter performance.

Representative envelope for the R245fa circuit, redrawn from the Xecom / Embraco Nidec scroll compressor selection guide, “Operating Envelop”, XD*G panel. Envelope limits are broadly similar across compressor makes, so treat this as a representation of the circuit’s operating window. Where a duty sits close to a boundary, confirm against the compressor fitted to the unit before finalising the design.