Technical Data Sheet · Water Source Heat Pump
SE-WW Series

SE-WW-95V

Water source heat pump giving hot and chilled water at the same time, hot water up to 60 °C. R410A circuit, shell-and-tube exchangers, three-phase. No fan and no air coil.

Sunniva SE-WW-95V water source heat pump unit
Heating output
95kW
At the rated condition
Cooling output
79.5kW
Simultaneous with heating
Max water temp
60°C
Rated outlet 55 °C
Heating COP
4.9
Source 15 °C · use 15 → 55 °C

Performance

Rated output at each published test condition
Rated Source 15 °C · use 15 → 55 °C
Heating output
95kW
Cooling output
79.5kW
Power input
19.4kW
Heating COP
4.9
Water flow (use side)
16.3m³/hr
Water flow (source side)
12.7m³/hr

Technical specifications

SE-WW-95V
Technical specifications for SE-WW-95V
ParameterUnitSpecification
Electrical supply
Power supply—380~415 V / 50 Hz / 3 Ph
Rated input powerkW19.4
Refrigeration circuit
Compressor—Scroll (Copeland)
Refrigerant—R410A
Heat exchanger (condenser)—Shell and tube
Evaporator—Shell and tube
Water circuit
Rated heating outputkW95
Rated cooling outputkW79.5
Heating COP—4.9
Hot water outputLPH2043
Rated water temperature°C55
Maximum water temperature°C60
Minimum water temperature°C7
Water flow (use side)m³/hr16.3
Water flow (source side)m³/hr12.7
Unit & acoustics
Dimensions (L × W × H)mm1800 × 1150 × 1050
Net weightkg730
Noise at 1 metredB(A)≤ 65

Test conditions

  • Rated — Source side inlet water 15 °C; use side inlet 15 °C, outlet 55 °C. Heating and cooling delivered at the same time.
  • At a different source temperature the output changes — ask Sunniva for the duty at your source.

Installation requirement

  • Maintain water flow of 16.3 m³/hr through the unit on the use side, and 12.7 m³/hr on the source side.
  • Source-side and use-side circuits are separate — both must be flowing before the unit will run.
  • Protection device and cable size are not published for this model. Confirm both with Sunniva before wiring.

Built to order

Options available on this model

Options

  • Water connection — Coupling type to suit the site — threaded, flanged or grooved.
  • Casing — Stainless steel or powder-coated finish.
  • Circulation pump — Can be built into the unit instead of being fitted in the plant room.
  • Condenser — Stainless steel or copper, in place of the standard build.

How to order them

  • None of the above is the standard build, and none of it is included in the specification table on this page.
  • Ask for it at enquiry and have it confirmed in writing on the order acknowledgement. Price, lead time and weight can all change with it.

The table above describes the standard machine. Options are quoted per order and are available across the range except on the All-in-One and Split units.

Site installation schematic

How the source loop and the delivery loop connect on site
SE-WWSE-WW-95VNo fan · no air clearanceHEAT SOURCEProcess return, condenserwater, or another heatpump’s reject sideIVYP1PIIVSource inCooled water back to sourceHOT WATER LOADHot water at 55 °Crated, 60 °C maximumIVPIPRVP2Y55 °C outReturnExpansion vesselExpansion vesselWarm source flowCooled source returnHot water to loadIV isolation valve · Y strainer · P circulating pump · PI pressure indicator · PRV pressure relief valveThere is no storage tank, no cold water feed and no potable draw-off on this machine.Both circuits are closed and both must be running before the compressor will start.

Indicative hookup only. Static head, draw pattern and local code may call for additional components — confirm the final scheme with Sunniva before ordering.

Selection & site preparation

Recommended sizing derived from this model’s rated data
System sizing
DutySimultaneous heating and cooling — the machine is rated into a process circuit, not into storage
Use-side circulation pump17.4 m³/hr @ 10 – 12 m head
Source-side circulation pump13.6 m³/hr @ 10 – 12 m head sized on the source-side flow, which is a different figure from the use side
Heat the source must take back79.5 kW of cooling at the rated duty — this is the chilled-water benefit, and the source loop must be able to use or reject it
Circuit separationSource and use circuits are hydraulically separate
Line insulation25 mm closed-cell on every line above 45 °C
Civil & electrical
Unit footprint & dry weight1800 × 1150 mm · 730 kg
Heat pump plinth1950 × 1300 × 150 mm RCC, M20
Plinth level100 mm above finished floor, ± 3 mm/m
Clearances1000 mm service side for the exchanger end covers — no air clearance required, there is no fan
ElectricalNot published for this model — confirm with Sunniva

Installation steps

Follow in order — a commissioning engineer should sign off before start-up
  1. Cast the RCC plinth 1950 × 1300 × 150 mm in M20 concrete, 100 mm above finished floor. Let it cure and check it is level within 3 mm per metre.
  2. Set the unit down on anti-vibration pads. It needs no air clearance, but leave 1000 mm on the service side for the exchanger end covers.
  3. Pipe the source side and the use side to their own circuits. They are separate — do not cross-connect them.
  4. Fit a Y-strainer and an isolation valve in each circuit before the unit, and a non-return valve after each pump.
  5. Insulate every line above 45 °C with 25 mm closed-cell, pump body included.
  6. Confirm the protection device and cable with Sunniva before wiring — they are not published for this model.
  7. Fill and vent both circuits fully. Confirm the flow switch stops the unit when a pump is off, then start.

Process & instrumentation diagram

Refrigeration circuit, instrumentation and water connections
EVAPORATORShell and tubeCONDENSERShell and tubeCOMPRESSORScroll · R410AELECTRONIC EXPANSION VALVELiquid lineSuction vapourDischarge · hot gasLiquid lineSOURCE WATER INCHILLED / SOURCE RETURNProcess return, condenser water,or the reject side of another heat pumpHOT WATER OUT · 55 °CRETURN · USE SIDEHot water to 60 °C maximumP1P2No air-side coil and no fan. Both sides of this machineare water, and the source circuit is not optional.

Instrument schedule

Tags as marked on the diagram above
TagDeviceFunction
TT 01Compressor discharge temperatureDischarge superheat & high-temperature cut-out
TT 02Compressor suction temperatureSuction superheat monitoring
TT 03Water outlet temperatureSet-point control
TT 04Water inlet temperatureReturn water sensing, ΔT calculation
PS HIGHHigh-pressure switchDischarge over-pressure cut-out
TagDeviceFunction
PS LOWLow-pressure switchLoss-of-charge / low-suction cut-out
PI HPHigh-side pressure gaugeDischarge pressure indication
PI LPLow-side pressure gaugeSuction pressure indication
FS 01Water flow switchInterlock — no-flow lockout

Operating envelope

The compressor’s permitted window, in refrigeration terms
Operating envelope · R410A circuit Condensing against evaporating temperature — the compressor’s permitted operating window
67 °C max condensing 102030405060708090 −30−20−100102030 Tc °C CONDENSING Te °C EVAPORATING Normal operation
Envelope limits
Evaporating temperature Te−25 °C to 25 °C
Condensing temperature Tc20 °C to 67 °C
Peak condensing67 °C the circuit’s figure — this model’s published water limit is 60 °C
Transient operationNot applicable the envelope above is the continuous operating window

Reading the envelope

  • Te (evaporating) follows the source the unit draws heat from — the colder the air or source water, the lower Te sits.
  • Tc (condensing) follows the water leaving the unit — asking for 80 °C hot water puts Tc near the top of the envelope.
  • A duty is valid only inside the shaded area. A cold source combined with very hot water pushes the point towards the top-left, which is exactly where the envelope closes in — that corner is the real limit on winter performance.

Representative envelope for the R410A circuit, redrawn from Panasonic compressor data (Operating envelop.xlsx, sheet “R410a”). Envelope limits are broadly similar across compressor makes, so treat this as a representation of the circuit’s operating window. Where a duty sits close to a boundary, confirm against the compressor fitted to the unit before finalising the design.

Documents & links

Scan with a phone camera, or tap the buttons

Talk to Sunniva

Scan to open a WhatsApp chat

Documentation

Scan to open the latest revision on sunnivaencon.com

Connect & review

Product videos and customer feedback

SE-WW-95V · Technical Data Sheet. Specifications are subject to change without prior notice.