SE-WW-55V
Water source heat pump giving hot and chilled water at the same time, hot water up to 60 °C. R410A circuit, shell-and-tube exchangers, three-phase. No fan and no air coil.
Performance
Rated output at each published test condition- Heating output
- 55kW
- Cooling output
- 43.4kW
- Power input
- 11.6kW
- Heating COP
- 4.75
- Water flow (use side)
- 9.4m³/hr
- Water flow (source side)
- 7.4m³/hr
Technical specifications
SE-WW-55V| Parameter | Unit | Specification |
|---|---|---|
| Electrical supply | ||
| Power supply | — | 380~415 V / 50 Hz / 3 Ph |
| Rated input power | kW | 11.6 |
| Refrigeration circuit | ||
| Compressor | — | Scroll (Copeland) |
| Refrigerant | — | R410A |
| Heat exchanger (condenser) | — | Shell and tube |
| Evaporator | — | Shell and tube |
| Water circuit | ||
| Rated heating output | kW | 55 |
| Rated cooling output | kW | 43.4 |
| Heating COP | — | 4.75 |
| Hot water output | LPH | 1182 |
| Rated water temperature | °C | 55 |
| Maximum water temperature | °C | 60 |
| Minimum water temperature | °C | 7 |
| Water flow (use side) | m³/hr | 9.4 |
| Water flow (source side) | m³/hr | 7.4 |
| Unit & acoustics | ||
| Dimensions (L × W × H) | mm | 1100 × 800 × 800 |
| Net weight | kg | 320 |
| Noise at 1 metre | dB(A) | ≤ 62 |
Test conditions
- Rated — Source side inlet water 15 °C; use side inlet 15 °C, outlet 55 °C. Heating and cooling delivered at the same time.
- At a different source temperature the output changes — ask Sunniva for the duty at your source.
Installation requirement
- Maintain water flow of 9.4 m³/hr through the unit on the use side, and 7.4 m³/hr on the source side.
- Source-side and use-side circuits are separate — both must be flowing before the unit will run.
- Protection device and cable size are not published for this model. Confirm both with Sunniva before wiring.
Built to order
Options available on this modelOptions
- Water connection — Coupling type to suit the site — threaded, flanged or grooved.
- Casing — Stainless steel or powder-coated finish.
- Circulation pump — Can be built into the unit instead of being fitted in the plant room.
- Condenser — Stainless steel or copper, in place of the standard build.
How to order them
- None of the above is the standard build, and none of it is included in the specification table on this page.
- Ask for it at enquiry and have it confirmed in writing on the order acknowledgement. Price, lead time and weight can all change with it.
The table above describes the standard machine. Options are quoted per order and are available across the range except on the All-in-One and Split units.
Site installation schematic
How the source loop and the delivery loop connect on siteIndicative hookup only. Static head, draw pattern and local code may call for additional components — confirm the final scheme with Sunniva before ordering.
Selection & site preparation
Recommended sizing derived from this model’s rated data| Duty | Simultaneous heating and cooling — the machine is rated into a process circuit, not into storage |
| Use-side circulation pump | 10.1 m³/hr @ 10 – 12 m head |
| Source-side circulation pump | 7.9 m³/hr @ 10 – 12 m head sized on the source-side flow, which is a different figure from the use side |
| Heat the source must take back | 43.4 kW of cooling at the rated duty — this is the chilled-water benefit, and the source loop must be able to use or reject it |
| Circuit separation | Source and use circuits are hydraulically separate |
| Line insulation | 25 mm closed-cell on every line above 45 °C |
| Unit footprint & dry weight | 1100 × 800 mm · 320 kg |
| Heat pump plinth | 1250 × 950 × 150 mm RCC, M20 |
| Plinth level | 100 mm above finished floor, ± 3 mm/m |
| Clearances | 1000 mm service side for the exchanger end covers — no air clearance required, there is no fan |
| Electrical | Not published for this model — confirm with Sunniva |
Installation steps
Follow in order — a commissioning engineer should sign off before start-up- Cast the RCC plinth 1250 × 950 × 150 mm in M20 concrete, 100 mm above finished floor. Let it cure and check it is level within 3 mm per metre.
- Set the unit down on anti-vibration pads. It needs no air clearance, but leave 1000 mm on the service side for the exchanger end covers.
- Pipe the source side and the use side to their own circuits. They are separate — do not cross-connect them.
- Fit a Y-strainer and an isolation valve in each circuit before the unit, and a non-return valve after each pump.
- Insulate every line above 45 °C with 25 mm closed-cell, pump body included.
- Confirm the protection device and cable with Sunniva before wiring — they are not published for this model.
- Fill and vent both circuits fully. Confirm the flow switch stops the unit when a pump is off, then start.
Process & instrumentation diagram
Refrigeration circuit, instrumentation and water connectionsInstrument schedule
Tags as marked on the diagram above| Tag | Device | Function |
|---|---|---|
| TT 01 | Compressor discharge temperature | Discharge superheat & high-temperature cut-out |
| TT 02 | Compressor suction temperature | Suction superheat monitoring |
| TT 03 | Water outlet temperature | Set-point control |
| TT 04 | Water inlet temperature | Return water sensing, ΔT calculation |
| PS HIGH | High-pressure switch | Discharge over-pressure cut-out |
| Tag | Device | Function |
|---|---|---|
| PS LOW | Low-pressure switch | Loss-of-charge / low-suction cut-out |
| PI HP | High-side pressure gauge | Discharge pressure indication |
| PI LP | Low-side pressure gauge | Suction pressure indication |
| FS 01 | Water flow switch | Interlock — no-flow lockout |
Operating envelope
The compressor’s permitted window, in refrigeration terms| Evaporating temperature Te | −25 °C to 25 °C |
| Condensing temperature Tc | 20 °C to 67 °C |
| Peak condensing | 67 °C the circuit’s figure — this model’s published water limit is 60 °C |
| Transient operation | Not applicable the envelope above is the continuous operating window |
Reading the envelope
- Te (evaporating) follows the source the unit draws heat from — the colder the air or source water, the lower Te sits.
- Tc (condensing) follows the water leaving the unit — asking for 80 °C hot water puts Tc near the top of the envelope.
- A duty is valid only inside the shaded area. A cold source combined with very hot water pushes the point towards the top-left, which is exactly where the envelope closes in — that corner is the real limit on winter performance.
Representative envelope for the R410A circuit, redrawn from Panasonic compressor data (Operating envelop.xlsx, sheet “R410a”). Envelope limits are broadly similar across compressor makes, so treat this as a representation of the circuit’s operating window. Where a duty sits close to a boundary, confirm against the compressor fitted to the unit before finalising the design.
Documents & links
Scan with a phone camera, or tap the buttonsDocumentation
Scan to open the latest revision on sunnivaencon.com
Connect & review
Product videos and customer feedback
SE-WW-55V · Technical Data Sheet. Specifications are subject to change without prior notice.