Sunniva Encon LLP · Application NoteAN-012 · Rev 0 · 23 Oct 2026
Dairy and food processing

Kettle cooking on pressurised hot water

How a ready-to-eat food plant cooking 6 tonnes of dal and gravies a day can heat its kettles with pressurised heat pump hot water instead of an LPG-fired boiler.

Application#12 Jacketed kettle cooking for ready-to-eat foods, gravies and dal
Temperature band95–115 °C
Sunniva selectionSE-UHT air-source cascade, ~60 kW
ReplacesLPG-fired steam boiler

▶Video: Process hot water for food, dairy and beverages

V02 · 2–2.5 min
Process hot water for food, dairy and beverages

Pasteurisers, CIP, cooking and washing on stored hot water instead of boiler steam

Video coming soon

01Problem statement

  • Burn-on at the kettle wall. Steam jackets at 2–3 bar make the wall hot enough to scorch thick gravies and dal if stirring slows.
  • Long simmer times. Dal and gravies simmer for an hour or more, so jackets draw heat for most of the shift.
  • Small plant, full boiler. Running a boiler, its attendant and its water treatment for eight kettles is a large overhead.
  • Losses between fuel and process. Burning LPG in a boiler or heater and distributing the heat loses a quarter or more of the fuel's energy before it reaches the process.
  • Compliance, safety and handling. Fired equipment brings boiler inspections, fuel storage and unloading, flue emissions and an attendant on every shift.

02Use case

The reference plant makes ready-to-eat dal, curries and gravies for retail packs and food service. Eight 300-litre tilting jacketed kettles cook about 6 tonnes of product a day over two shifts. Kettles and utensils are washed with hot water.

Heat userProcess temp.BasisHeat, kWh/day
Kettle batches, heating25 → 97 °C6,000 kg product/day, 15% jacket and lid losses511
Simmering and evaporation95–98 °C8 kettles × 4 kW × 6 h192
Kettle and utensil washing65 °C4,000 L/day, 30 → 65 °C163
Storage and pipework standing losses–about 5%43
Total useful heat908

Averaged over 16 running hours, the heat pumps need about 57 kW.

03P&ID

L-101 · Hot primary · 120 °CTT103L-102 · Return · ~90 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101~60 kW, built to dutyAir-source, outdoorTK-1012,000 L120 °CinsulatedventTT101TT102LT101softenermake-up waterVFDP-102A/BL-201 · Supply header · 118 °CTCV-201TIC201TK-201Kettle jackets97 °C productproduct in 25 °Ccooked 97 °CTCV-202TIC202PHE-202Wash water heater65 °CL-202 · Return header · ~90 °CNCB-001 existing LPG heaterstandby / top-up onlyhot supplyreturnsignalpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-012 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • A SE-UHT air-source cascade, R245fa machine of about 60 kW, air-source cascade to 120 °C, sized per project.
  • A 2,000 L insulated storage tank decouples the heat pumps from the process peaks.
  • The LPG-fired steam boiler stays connected behind a normally closed valve as standby.
  • Pressurised hot water at 115–120 °C circulates through the kettle jackets in place of steam.
  • Each kettle has its own valve and temperature controller, so the cook can hold a gentle simmer.
  • Wash water is heated from the same loop through a plate exchanger.

Selected equipment

MachineSE-UHT air-source cascade, R245fa
Capacityabout 60 kW, built to duty
Conceptair-source cascade to 120 °C, sized per project
COP used1.6 (estimate)
Supply temperature120 °C
Storage2,000 L insulated tank

Capacity is sized from the heat demand above. COP is an estimate until Sunniva engineering confirms the design.

Control philosophy

TT-101 at the tank top starts the heat pumps below 112 °C and stops them at 120 °C. TIC-201 on each kettle controls jacket flow for heating and then a lower simmer setting. TT-102 at the tank bottom gives an early start before the morning batches. If the tank falls below 105 °C, the standby steam supply to the jackets is enabled.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per tonne of product––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

Less scorching

Jacket water at 115–120 °C is gentler than steam, so product sticks less.

Easier simmer control

A flow valve gives smooth, low heat for simmering.

No IBR boiler for cooking

Kettles run without a steam boiler, attendant or condensate system.

Lower energy cost

Each kWh of electricity delivers about 1.6 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

No flame on site

No burner, flue or fuel tank for this duty, and no fuel deliveries to schedule.

Solar-ready

Running hours can be placed in daylight so rooftop solar supplies much of the electricity, which also cuts CO₂ further.

07Engineering pointers

Site data to collect

  • Number and size of kettles
  • Products, batch sizes and cook times
  • Jacket type and pressure rating
  • Washing water use
  • Current LPG or steam use per day
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access
  • Winter minimum ambient at site

Design notes

  • Jacket rating. Check kettle jackets are rated for the loop pressure, and that they have inlet and outlet connections suited to water flow.
  • Heating time. Hot water heats more slowly than steam at first. Allow for this in batch planning or preheat ingredients.
  • Pressurised loop. Hold the loop above about 2.5 bar(g) to keep water at 120 °C from flashing.
  • Ambient correction. Ratings are at 20 °C air. Ask Sunniva for the correction at your site's winter design temperature.
  • Water quality. Scale forms quickly above 60 °C. Use softened make-up and keep the heat pump loop closed, with process fluids on the far side of an exchanger or coil.
  • Performance figure. The COP on this page is an engineering estimate, not a data sheet value. Sunniva engineering will confirm it for the actual source and supply temperatures.