Sunniva Encon LLP · Application NoteAN-102 · Rev 0 · 23 Oct 2026
Agro-industrial and aquaculture

Chick brooding and hatchery heat without LPG

How a broiler hatchery with two 1,000 m² brooding houses can supply its room and floor heating with heat pumps, and what it saves against LPG gas brooders and heaters.

Application#102 Poultry hatcheries and brooders
Temperature band30–35 °C
Sunniva selection1 × SE-AH-140V
ReplacesLPG gas brooders and space heaters

▶Video: Space heating for buildings and farms

V13 · 2–2.5 min
Space heating for buildings and farms

Floor heating, fan coils and air handlers, from homes to poultry sheds

Video coming soon

01Problem statement

  • Chicks cannot keep themselves warm. Day-old chicks need 32–35 °C at floor level. Cold floors cause huddling, poor feed intake and early losses.
  • Gas brooders add moisture and fumes. Open-flame LPG brooders release water vapour and combustion gases into the house, which worsens litter and air quality.
  • Hatchery room air. Setter and hatcher rooms need large volumes of fresh air at a steady 24–27 °C, which is costly to heat in winter.
  • Losses between fuel and process. Burning LPG in a boiler or heater and distributing the heat loses a quarter or more of the fuel's energy before it reaches the process.
  • Compliance, safety and handling. Fired equipment brings boiler inspections, fuel storage and unloading, flue emissions and an attendant on every shift.

02Use case

The reference unit in north India runs a hatchery setting about 60,000 eggs a week and two 1,000 m² brooding houses for day-old chicks. Winter nights fall to 3–5 °C, and chicks need 32–35 °C at floor level in their first week.

Heat userProcess temp.BasisHeat, kWh/day
Brooding house floor heatingFloor 30–35 °C2 houses × 1,000 m² × 40 W/m² × 16 h1,280
Hatchery fresh-air heatingSupply air 26 °C20,000 m³/h × 1.2 kg/m³ × 1.005 kJ/kgK × 10 K = 67 kW × 10 h670
Hatchery and equipment washing55 °C5,000 L/day, 25 → 55 °C174
Storage and pipework standing losses–about 5%106
Total useful heat2,230

Averaged over 18 running hours, the heat pumps need about 124 kW.

03P&ID

L-101 · Hot primary · 50 °CTT103L-102 · Return · ~38 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101SE-AH-140V · 140 kWAir-source, outdoorTK-1014,500 L50 °CinsulatedventTT101TT102LT101softenermake-up waterVFDP-102A/BL-201 · Supply header · 48 °CTCV-201TIC201FL-201Brooder floor loops30–35 °C floorreturn 35 °Csupply 45 °CTCV-202TIC202AHU-202Hatchery fresh-air AHU26 °C airTCV-203TIC203DR-203Washing hot water55 °CL-202 · Return header · ~38 °CNCB-001 existing LPG heaterstandby / top-up onlyhot supplyreturnsignalpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-102 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • 1 × SE-AH-140V (140 kW) (SE-AH air-source heat pump) delivering 50 °C, covering the day's 2,230 kWh in about 15.9 running hours.
  • A 4,500 L insulated storage tank decouples the heat pumps from the process peaks.
  • The LPG gas brooders and space heaters stays connected behind a normally closed valve as standby.
  • PEX floor heating loops under the brooding area keep the litter and floor warm, with zone valves for each pen.
  • A hot-water coil in the hatchery fresh-air AHU replaces gas or electric air heaters.
  • The same tank supplies hot water for tray, trolley and floor washing.
  • Ventilation can now be set for air quality alone, because heating no longer adds moisture or fumes.

Selected equipment

ModelSE-AH-140V × 1
Heating capacity140 kW each, 140 kW total
COP4.1 at A20 °C / W50 °C (data sheet T1)
Power inputabout 34.1 kW total at rated conditions
Ratingrated 55 °C, 60 °C maximum, R410A
Supply temperature50 °C
Storage4,500 L insulated tank

Ratings from the Sunniva TDS 2026 data sheets.

Control philosophy

TT-101 at the top of the tank starts the heat pumps below 45 °C and stops them at 50 °C. TIC-201 holds each brooding zone at its set floor temperature, stepping down week by week as chicks grow. TIC-202 holds hatchery supply air at 26 °C. LPG brooders stay as standby for extreme cold.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per 1,000 chicks placed––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

Drier litter

No combustion moisture in the house, so litter stays drier and ammonia stays lower.

Even warmth across the floor

Floor heating spreads chicks out instead of crowding them under a few brooders.

Better early growth

Steady temperature in the first week supports feed intake and uniform weights.

Lower energy cost

Each kWh of electricity delivers about 4.1 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

No flame on site

No burner, flue or fuel tank for this duty, and no fuel deliveries to schedule.

Solar-ready

Running hours can be placed in daylight so rooftop solar supplies much of the electricity, which also cuts CO₂ further.

07Engineering pointers

Site data to collect

  • House sizes, floor construction and insulation
  • Chick placement schedule and target temperatures by week
  • Hatchery ventilation rates
  • Current LPG use per flock
  • Lowest winter temperatures at site
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access
  • Winter minimum ambient at site

Design notes

  • Biosecurity. Keep heat pump units outside the clean zone and route pipework so maintenance staff do not enter houses.
  • Floor build-up. Lay insulation under the floor loops so heat goes up into the litter and not into the ground.
  • Ammonia exposure. Place outdoor units away from exhaust fans, as ammonia-laden air corrodes fins.
  • Electrical. About 34 kW of heat pump input at rated conditions, plus pumps and fans. Check spare sanctioned load before ordering.
  • Winter output. Air-source output falls in cold weather: about two-thirds of rated capacity at 5 °C ambient. Size on the coldest design day for northern sites.

Service and warranty

Sunniva has supplied 5,000+ heat pumps since 2012, with nine service technicians across India, including remote sites such as Leh. All components carry a one-year warranty.