How a tannery processing 5 tonnes of wet-blue a day can make all its 35–60 °C drum water with heat pumps, against a diesel-fired hot-water generator.

Application#58 Leather tanning and retanning drums
Temperature band35–60 °C
Sunniva selection4 × SE-SHT-16C
Replacesdiesel-fired hot-water generator

▶Video: Heat pumps for textile and leather processing

V03 · 2–2.5 min
Heat pumps for textile and leather processing

Dyeing, pre-treatment and tanning, with heat recovered from hot drain water

Video coming soon

01Problem statement

  • Precise floats need precise water. Retanning and fatliquoring floats must be at 50 to 60 °C. Water that is too hot spoils the emulsion, and water that is too cool slows penetration.
  • Mixing hot and cold by hand. Operators often blend boiler water with cold water at the drum, so float temperatures vary batch to batch.
  • Low-temperature job, high-temperature fuel. A fired generator burning diesel is used for water that only needs to reach 60 °C.
  • Losses between fuel and process. Burning diesel in a boiler or heater and distributing the heat loses a quarter or more of the fuel's energy before it reaches the process.
  • Compliance, safety and handling. Fired equipment brings boiler inspections, fuel storage and unloading, flue emissions and an attendant on every shift.

02Use case

The reference tannery processes 5 tonnes of shaved wet-blue a day into crust and finished leather. Drums run pickling, tanning, retanning, dyeing and fatliquoring on two shifts.

Heat userProcess temp.BasisHeat, kWh/day
Fatliquoring floats55–60 °C5,000 kg × 1.5 L/kg = 7,500 L, 28 → 60 °C279
Retanning and dyeing floats40–50 °C5,000 kg × 2 L/kg = 10,000 L, 28 → 50 °C255
Pickling and tanning floats35–40 °C10,000 L/day, 28 → 40 °C139
Warm washes45 °C15,000 L/day, 28 → 45 °C296
Storage and pipework standing losses–about 5%48
Total useful heat1,018

Averaged over 20 running hours, the heat pumps need about 51 kW.

03P&ID

L-101 · Hot primary · 65 °CTT103L-102 · Return · ~49 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101SE-SHT-16C · 16 kWHP-102…104SE-SHT-16C · 16 kWAir-source, outdoorTK-1012,000 L65 °CinsulatedventTT101TT102LT101softenermake-up waterVFDP-102A/BL-201 · Supply header · 63 °CTCV-201TIC201PHE-201Drum fill water heater60 °Cfresh water 28 °Cto drums 60 °CTCV-202TIC202TK-202Warm wash water tank45 °CL-202 · Return header · ~49 °CNCB-001 existing diesel boilerstandby / top-up onlyhot supplyreturnsignalpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-058 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • 4 × SE-SHT-16C (64 kW total) (SE-SHT cascade heat pump) delivering 65 °C, covering the day's 1,018 kWh in about 15.9 running hours.
  • A 2,000 L insulated storage tank decouples the heat pumps from the process peaks.
  • The diesel-fired hot-water generator stays connected behind a normally closed valve as standby.
  • The heat pumps charge a storage tank at 65 °C. Fresh drum water is heated through PHE-201 so drum water never mixes with the heating loop.
  • Thermostatic mixing at each drum header delivers floats at the recipe temperature.
  • A separate warm wash tank at 45 °C covers the large wash volumes between process steps.

Selected equipment

ModelSE-SHT-16C × 4
Heating capacity16 kW each, 64 kW total
COP2.7 at A20 °C / W90 °C (data sheet T1)
Power inputabout 23.8 kW total at rated conditions
Ratingcascade R410A + R515B, rated 90 °C, 95 °C maximum
Supply temperature65 °C
Storage2,000 L insulated tank

Ratings from the Sunniva TDS 2026 data sheets.

Control philosophy

TT-101 starts the heat pumps below 60 °C and stops them at 65 °C. TIC-201 holds the drum fill water at set-point, and TIC-202 keeps the wash tank at 45 °C. The diesel generator stays as standby for peak days.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per tonne of wet-blue––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

Repeatable floats

Water at the right temperature for each step gives more even dye uptake and fatliquor penetration.

Low-temperature efficiency

At 65 °C supply the heat pumps run at a high efficiency all year.

Ready at batch start

Stored hot water fills drums at once, so drum cycles start on time.

Lower energy cost

Each kWh of electricity delivers about 2.7 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

No flame on site

No burner, flue or fuel tank for this duty, and no fuel deliveries to schedule.

Built-in redundancy

Several machines share the load. If one is serviced, the others and the storage carry most of the day, with the existing heater in reserve.

07Engineering pointers

Site data to collect

  • Wet-blue or rawhide processed per day
  • Float ratios and temperatures per process step
  • Number of drums and fill schedule
  • Present diesel use for hot water
  • Water hardness
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access
  • Winter minimum ambient at site

Design notes

  • Chrome and acids. Keep the heating loop closed and away from tanning floats. Use stainless steel on the fresh-water side of PHE-201.
  • Corrosive atmosphere. Tannery air carries hydrogen sulphide and ammonia. Site heat pumps upwind of beamhouse and ETP, and specify coated coils.
  • Water hardness. Soft water helps both leather quality and the exchanger. Use softened water for fill if available.
  • Electrical. About 24 kW of heat pump input at rated conditions, plus pumps and fans. Check spare sanctioned load before ordering.
  • Winter output. The SE-SHT cascade gives about 80% of rated output at 7 °C ambient and still runs at −20 °C. Size on the coldest design day for northern sites.
  • Water quality. Scale forms quickly above 60 °C. Use softened make-up and keep the heat pump loop closed, with process fluids on the far side of an exchanger or coil.

Service and warranty

Sunniva has supplied 5,000+ heat pumps since 2012, with nine service technicians across India, including remote sites such as Leh. All components carry a one-year warranty.