Sunniva Encon LLP · Application NoteAN-026 · Rev 0 · 23 Oct 2026
Dairy and food processing

Ripening chambers heated with recovered chiller heat

How a 10-chamber banana and mango ripening centre can reuse heat from its own chillers for room heating and crate washing, and what it saves against electric heaters.

Application#26 Fruit ripening chambers (heating and cooling at the same time)
Temperature band18–20 °C rooms, 55 °C wash
Sunniva selection1 × SE-WW-55V
Replaceselectric duct heaters and water heaters

▶Video: Heating and cooling from one machine

V11 · 2–2.5 min
Heating and cooling from one machine

Water-source heat pumps that chill and heat at the same time

Video coming soon

01Problem statement

  • Heating and cooling in the same building. Freshly loaded fruit has to be warmed to start ripening while other rooms are being cooled to remove respiration heat. Chillers reject heat outdoors and electric heaters add it back a few metres away.
  • Tight pulp temperature control. Bananas need pulp held within about 1 K. Electric heaters cycling on and off cause swings that give uneven colour and short shelf life.
  • High electricity bill. Electric heaters run at a COP of 1, so room reheat and hot water for crates are a large share of the centre's power bill.
  • Electric heating is expensive heat. Resistance heaters turn one kWh of electricity into one kWh of heat, at the full commercial tariff. A heat pump moves two to four kWh of heat for the same unit.
  • Large connected load. Heater banks take a big share of the sanctioned load and push up maximum-demand charges.

02Use case

The reference centre has 10 ethylene ripening chambers of 20 tonnes each, handling bananas most of the year and mangoes in season. Two chambers are loaded and two dispatched every day on a 4 to 5 day cycle. Plastic crates are washed on site before reuse.

Heat userProcess temp.BasisHeat, kWh/day
Warming newly loaded fruitPulp 13 → 18 °C2 rooms/day × 20 t × 3.6 kJ/kg·K × 5 K200
Room reheat for humidity control18–20 °C10 rooms × 2 kW × 12 h240
Crate washing55 °C6,000 L/day, 28 → 55 °C188
Storage and pipework standing losses–about 5%31
Total useful heat660

Averaged over 18 running hours, the heat pumps need about 37 kW.

03P&ID

L-101 · Hot primary · 50 °CTT103L-102 · Return · ~38 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101SE-WW-55V · 55 kWP-100SRC-100ripening-room chillercondenser waterheat source ~32 °CWater-sourceTK-1012,000 L50 °CinsulatedventTT101TT102LT101softenermake-up waterVFDP-102A/BL-201 · Supply header · 48 °CTCV-201TIC201AHU-201Ripening room coils18–20 °Croom air 14 °Croom air 20 °CTCV-202TIC202PHE-202Crate washer55 °CL-202 · Return header · ~38 °CNCB-001 existing electric heatersstandby / top-up onlyhot supplyreturnsignalsource waterpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-026 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • 1 × SE-WW-55V (55 kW) (SE-WW water-source heat pump) delivering 50 °C, covering the day's 660 kWh in about 12.0 running hours.
  • A 2,000 L insulated storage tank decouples the heat pumps from the process peaks.
  • Heat source: ripening-room chiller condenser water at about 32 °C. Drawing heat from the chiller condenser water lowers condensing pressure, so the room chillers use less power.
  • The electric duct heaters and water heaters stays connected behind a normally closed valve as standby.
  • The heat pumps take heat from the condenser water loop of the existing room chillers, so heat removed from ripening rooms is reused instead of rejected.
  • Each room unit gets a hot-water coil next to its cooling coil, so a room can be warmed or reheated without electric heaters.
  • Hot water at 50 °C is stored in a tank and also heats crate wash water through a plate exchanger.

Selected equipment

ModelSE-WW-55V × 1
Heating capacity55 kW each, 55 kW total
COP4.7 at the data sheet's rated condition (55 °C outlet)
Power inputabout 11.6 kW total at rated conditions
Ratinghot and chilled water at the same time, to 60 °C
Supply temperature50 °C
Storage2,000 L insulated tank

Ratings from the Sunniva TDS 2026 data sheets.

Control philosophy

TT-101 at the tank top calls the heat pumps on below 45 °C and off at 50 °C. TT-102 at the bottom starts a unit early when rooms are loaded in the morning. TIC-201 in each room opens the hot-water valve in step with the ripening programme, and TIC-202 holds the crate wash at 55 °C. The existing electric heaters stay as standby.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per tonne of ripened fruit––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

One heat flow, two jobs

Respiration heat taken out of ripening rooms warms the next batch of fruit and the crate wash.

Even colour

Modulating hot-water coils hold pulp temperature steadily, which gives more even ripening across a room.

Chillers work less

The chillers condense at a lower temperature when the heat pumps draw on their condenser water.

Lower energy cost

Each kWh of electricity delivers about 4.7 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

Smaller electrical load

The heat pump draws roughly 1/4.7 of the power of the heaters it replaces, which frees sanctioned load and cuts demand charges.

Solar-ready

Running hours can be placed in daylight so rooftop solar supplies much of the electricity, which also cuts CO₂ further.

07Engineering pointers

Site data to collect

  • Number and size of ripening rooms
  • Daily tonnes loaded and dispatched
  • Chiller capacity and condenser water flow
  • Present electric heater ratings and running hours
  • Crate wash volumes
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access

Design notes

  • Hydraulic separation. Connect to the chiller condenser loop through a plate exchanger or a decoupler, so the heat pumps never starve the chillers of condenser flow.
  • Ethylene and hygiene. Room coils should be stainless or coated copper with easy-clean fins. Drain pans must drain freely to avoid mould.
  • Low-temperature heating. Size room coils for 45–50 °C water. Coils sized for electric heater duty at higher air temperatures will be too small.
  • Electrical. About 12 kW of heat pump input at rated conditions, plus pumps and fans. Check spare sanctioned load before ordering.
  • Source stream. The source must give up roughly two-thirds of the heat delivered. Confirm its flow and temperature over a full production day, and filter it before the evaporator.