Pharma, chemicals and FMCG

Fermenter warm water from fermenter cooling heat

How a biotech plant can warm its fermenters, media and downstream water to 30–45 °C with a heat pump on fermenter cooling-water return, in place of electric heaters.

Application#65 Fermentation and biotech temperature control
Temperature band30–40 °C
Sunniva selection1 × SE-WW-55V
Replaceselectric immersion heaters

▶Video: Waste-heat recovery heat pumps

V10 · 2–2.5 min
Waste-heat recovery heat pumps

Lifting warm water from condensers, effluent and process cooling to useful heat

Video coming soon

01Problem statement

  • Heating and cooling at the same time. Fermenters reject heat to cooling water during growth, while media, seed and buffer water are heated electrically next door.
  • Tight temperature windows. Cultures need 30 to 40 °C within ±0.5 K. Electric heaters cycle on and off and can overshoot.
  • Power cost. Resistance heating of large water volumes is expensive per unit of heat.
  • Electric heating is expensive heat. Resistance heaters turn one kWh of electricity into one kWh of heat, at the full commercial tariff. A heat pump moves two to four kWh of heat for the same unit.
  • Large connected load. Heater banks take a big share of the sanctioned load and push up maximum-demand charges.

02Use case

The reference plant makes enzymes and probiotic cultures in three 10 m³ production fermenters with seed vessels. It runs batch fermentations around the clock with media preparation and downstream recovery on two shifts.

Heat userProcess temp.BasisHeat, kWh/day
Production fermenter warm-up25 → 37 °C2 batches × 10,000 L279
Media and seed water25 → 40 °C10,000 L/day174
Downstream wash and buffer water25 → 45 °C8,000 L/day186
Storage and pipework standing losses–about 5%32
Total useful heat671

Averaged over 20 running hours, the heat pumps need about 34 kW.

03P&ID

L-101 · Hot primary · 55 °CTT103L-102 · Return · ~41 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101SE-WW-55V · 55 kWP-100SRC-100fermentercooling-water returnheat source ~32 °CWater-sourceTK-1012,000 L55 °CinsulatedventTT101TT102LT101softenermake-up waterVFDP-102A/BL-201 · Supply header · 53 °CTCV-201TIC201TK-201Fermenter jackets37 °Cbroth 25 °Cbroth 37 °CTCV-202TIC202TK-202Media prep vessel40 °CTCV-203TIC203PHE-203Buffer water heater45 °CL-202 · Return header · ~41 °CNCB-001 existing electric heatersstandby / top-up onlyhot supplyreturnsignalsource waterpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-065 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • 1 × SE-WW-55V (55 kW) (SE-WW water-source heat pump) delivering 55 °C, covering the day's 671 kWh in about 12.2 running hours.
  • A 2,000 L insulated storage tank decouples the heat pumps from the process peaks.
  • Heat source: fermenter cooling-water return at about 32 °C. Cooling the fermenter return water reduces chiller or cooling tower load during the exothermic growth phase.
  • The electric immersion heaters stays connected behind a normally closed valve as standby.
  • Fermenter cooling-water return at about 32 °C passes through the heat pump evaporator and goes back to the fermenters colder.
  • The heat pump charges a warm-water tank at 50–55 °C that serves fermenter jackets, media preparation and downstream heaters.
  • The tank evens out the mismatch between batch warm-up demand and the cooling heat available during growth.

Selected equipment

ModelSE-WW-55V × 1
Heating capacity55 kW each, 55 kW total
COP4.7 at the data sheet's rated condition (55 °C outlet)
Power inputabout 11.6 kW total at rated conditions
Ratinghot and chilled water at the same time, to 60 °C
Supply temperature55 °C
Storage2,000 L insulated tank

Ratings from the Sunniva TDS 2026 data sheets.

Control philosophy

TT-101 holds the warm-water tank between 50 and 55 °C, with the heat pump enabled while cooling-water return is above 28 °C. TIC-201 controls each fermenter jacket in split range between warm and cooling water. Electric heaters stay as standby when the source runs short.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per fermentation batch––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

Cooling and heating together

One machine cools the fermenters and heats the media.

Steady culture temperature

Modulating warm-water control holds the broth within tight limits without overshoot.

Much lower power

The heat pump delivers several units of heat per unit of power at this small temperature lift.

Lower energy cost

Each kWh of electricity delivers about 4.7 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

Smaller electrical load

The heat pump draws roughly 1/4.7 of the power of the heaters it replaces, which frees sanctioned load and cuts demand charges.

Solar-ready

Running hours can be placed in daylight so rooftop solar supplies much of the electricity, which also cuts CO₂ further.

07Engineering pointers

Site data to collect

  • Fermenter volumes and batches per day
  • Culture temperature set-points
  • Cooling-water flow and temperatures during growth
  • Media and buffer water volumes
  • Present electric heater ratings
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access

Design notes

  • Sterility. Keep warm water in jackets and coils only. Media and broth are heated through closed surfaces.
  • Source timing. Cooling heat peaks mid-fermentation and warm-up demand peaks at batch start. Stagger batches and size the tank to bridge the gap.
  • Sterilisation stays on steam. Media and fermenter sterilisation need steam above the heat pump range. This note covers temperature control only.
  • Electrical. About 12 kW of heat pump input at rated conditions, plus pumps and fans. Check spare sanctioned load before ordering.
  • Source stream. The source must give up roughly two-thirds of the heat delivered. Confirm its flow and temperature over a full production day, and filter it before the evaporator.

Service and warranty

Sunniva has supplied 5,000+ heat pumps since 2012, with nine service technicians across India, including remote sites such as Leh. All components carry a one-year warranty.