Sunniva Encon LLP · Application NoteAN-073 · Rev 0 · 23 Oct 2026
Metal finishing and engineering

Anodising seal tanks heated by heat pumps

How an aluminium anodising plant finishing 8 tonnes of profiles a day can heat its hot seal tank with heat pumps, and what it saves against electric immersion heaters.

Application#73 Anodising seal tanks
Temperature band80–95 °C
Sunniva selectionSE-UHT air-source cascade, ~40 kW
Replaceselectric immersion heaters

▶Video: Process heat for engineering and utilities

V06 · 2–2.5 min
Process heat for engineering and utilities

Plating, phosphating, washers, curing and boiler feedwater

Video coming soon

01Problem statement

  • Seal tank is the biggest heat user. The seal tank runs near boiling, so it loses far more heat through evaporation than any other tank on the line.
  • Large loads cool the bath. Each rack of profiles drops the seal temperature, and seal quality falls if the bath stays below set point.
  • Heaters fail in hard water. Immersion elements scale quickly in seal water and burn out, stopping the line while the tank cools.
  • Electric heating is expensive heat. Resistance heaters turn one kWh of electricity into one kWh of heat, at the full commercial tariff. A heat pump moves two to four kWh of heat for the same unit.
  • Large connected load. Heater banks take a big share of the sanctioned load and push up maximum-demand charges.

02Use case

The reference plant anodises architectural aluminium extrusions. It runs two shifts and finishes about 8 tonnes of profiles a day through a single 5,000 L hot seal tank.

Heat userProcess temp.BasisHeat, kWh/day
Seal tank reheat after night cool-down50 → 92 °C5,000 L tank with lid, 42 K reheat each morning244
Evaporation from seal tank surface92 °C3 m² surface × 4 kW/m² × 16 h192
Aluminium profiles and racks30 → 90 °C8 t/day × 0.90 kJ/kg·K × 60 K120
Make-up for evaporation and drag-out30 → 92 °C1,500 L/day DI water, 30 → 92 °C108
Storage and pipework standing losses–about 5%33
Total useful heat697

Averaged over 18 running hours, the heat pumps need about 39 kW.

03P&ID

L-101 · Hot primary · 105 °CTT103L-102 · Return · ~79 °CY-STRP-101AP-101Bduty / standbyEXP-101FS101HP-101~40 kW, built to dutyAir-source, outdoorTK-1011,500 L105 °CinsulatedventTT101TT102LT101softenermake-up waterVFDP-102A/BL-201 · Supply header · 103 °CTCV-201TIC201TK-201Hot seal tank92 °CHW in 105 °CHW out 95 °CTCV-202TIC202TK-202DI make-up preheat90 °CL-202 · Return header · ~79 °CNCB-001 existing electric heatersstandby / top-up onlyhot supplyreturnsignalpumpvalvenormally closedINDICATIVE P&ID · NOT FOR CONSTRUCTIONAN-073 · Rev 0 · Sunniva Encon LLP

Tags: HP heat pump, TK tank, SG steam generator, P pump, PHE plate heat exchanger, TCV temperature control valve, TIC temperature indicating controller (panel), TT temperature transmitter, MT moisture transmitter, PT pressure transmitter, LT level transmitter, FS flow switch, NC normally closed. Process fluids are heated through their own exchanger, coil or jacket.

04Solution

System description

  • A SE-UHT air-source cascade, R245fa machine of about 40 kW, air-source cascade to 120 °C, sized per project.
  • A 1,500 L insulated storage tank decouples the heat pumps from the process peaks.
  • The electric immersion heaters stays connected behind a normally closed valve as standby.
  • A titanium or stainless steel 316 coil in the seal tank is fed with pressurised hot water at 105 °C.
  • DI make-up water is preheated in a separate coil tank before it enters the seal tank, so top-ups do not knock the bath temperature down.
  • One immersion heater is kept on trim duty to recover temperature after very heavy loads, and the rest stay as standby.

Selected equipment

MachineSE-UHT air-source cascade, R245fa
Capacityabout 40 kW, built to duty
Conceptair-source cascade to 120 °C, sized per project
COP used1.8 (estimate)
Supply temperature105 °C
Storage1,500 L insulated tank

Capacity is sized from the heat demand above. COP is an estimate until Sunniva engineering confirms the design.

Control philosophy

TT-101 at the tank top starts the heat pumps below 100 °C and stops them at 105 °C. TIC-201 holds the seal tank at 92 °C by modulating its coil valve. TIC-202 holds the make-up preheat tank at 90 °C. If the seal tank stays below 88 °C for 10 minutes the PLC enables the trim immersion heater.

05Energy saving and ROI

Change any input to match a customer's site. Defaults are typical Indian prices for October 2026. The installed cost is a placeholder; replace it with the actual quotation.

Plant
Existing heating
Heat pump
Annual saving–energy + O&M
Simple payback––
Purchased energy––
10-year net gain–after paying for the system
ExistingHeat pump
Daily consumption––
Annual energy cost––
Cost per tonne of aluminium anodised––
CO₂ per year––
Cumulative cash position, years 0–10

06Benefits

Consistent seal quality

Stored heat recovers the bath quickly after each rack, which helps meet seal quality tests.

Fewer heater burn-outs

The heat pump coil runs at a lower surface temperature than electric elements and scales more slowly.

Cheaper evaporation losses

The large, continuous evaporation load is met at a fraction of the cost of resistance heating.

Lower energy cost

Each kWh of electricity delivers about 1.8 kWh of heat at the required temperature, against well under one kWh of useful heat per kWh of fuel burnt.

Smaller electrical load

The heat pump draws roughly 1/1.8 of the power of the heaters it replaces, which frees sanctioned load and cuts demand charges.

Solar-ready

Running hours can be placed in daylight so rooftop solar supplies much of the electricity, which also cuts CO₂ further.

07Engineering pointers

Site data to collect

  • Seal tank volume, temperature and seal type
  • Tonnes of aluminium anodised per day
  • Tank surface area and lid arrangement
  • DI make-up volume per day
  • Present fuel or electricity use and monthly bill
  • Sanctioned electrical load and spare capacity
  • Space for the heat pumps and storage, with service access
  • Winter minimum ambient at site

Design notes

  • Pressurised loop. Water at 105 °C needs a pressurised loop of at least 3 bar with an expansion vessel and safety valve sized for it.
  • Seal water purity. Seal baths are sensitive to silicates and phosphates. Coil and fittings must not leach contaminants, so use titanium or stainless steel 316 only.
  • Cover the tank. A lid or floating balls on the seal tank can halve evaporation losses. Fit these before sizing the heat pumps.
  • Ambient correction. Ratings are at 20 °C air. Ask Sunniva for the correction at your site's winter design temperature.
  • Water quality. Scale forms quickly above 60 °C. Use softened make-up and keep the heat pump loop closed, with process fluids on the far side of an exchanger or coil.
  • Performance figure. The COP on this page is an engineering estimate, not a data sheet value. Sunniva engineering will confirm it for the actual source and supply temperatures.